All categories
Compare Cart

LC1F185FD - TeSys F contactor 3P (3 NO) AC3 <= 440 V 185 A coil 110 V DC - Schneider Electric

Expected in 2-4 weeks
LC1F185FD - TeSys F contactor 3P (3 NO) AC3 <= 440 V 185 A coil 110 V DC - Schneider Electric - TeSys F contactor 3P (3 NO) AC3 <= 440 V 185 A coil 110 V DC - Schneider Electric - 0
LC1F185FD - TeSys F contactor 3P (3 NO) AC3 <= 440 V 185 A coil 110 V DC - Schneider Electric
919,67 €
919,67 € incl. VAT
Text About:
TeSys F contactor 3P (3 NO) AC3 <= 440 V 185 A coil 110 V DC - Schneider Electric
919,67 €
SPECIFICATIONS
Main
Contactor application Resistive load
Motor control
Device short name LC1F
Range TeSys
[uc] control circuit voltage 110 V DC
[ui] rated insulation voltage 1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
control circuit type DC standard
motor power kW 90 kW at 380...400 V AC 50/60 Hz (AC-3)
100 kW at 415 V AC 50/60 Hz (AC-3)
100 kW at 440 V AC 50/60 Hz (AC-3)
110 kW at 500 V AC 50/60 Hz (AC-3)
110 kW at 660...690 V AC 50/60 Hz (AC-3)
55 kW at 220...230 V AC 50/60 Hz (AC-3)
33 kW at 400 V AC 50/60 Hz (AC-4)
average impedance 0.33 mOhm - Ith 275 A 50 Hz
Complementary
[ie] rated operational current 275 A (at <40 °C) at <= 440 V AC-1
185 A (at <55 °C) at <= 440 V AC-3
[ue] rated operational voltage <= 460 V DC
<= 690 V AC 50/60 Hz
compatibility code LC1F
[ics] rated service breaking capacity 1480 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current 1500 A 40 °C - 10 s
920 A 40 °C - 30 s
740 A 40 °C - 1 min
500 A 40 °C - 3 min
400 A 40 °C - 10 min
[ith] conventional thermal current 275 A (at 40 °C)
Product certifications RINA
BV
RMRoS
UL
CB
ABS
CSA
DNV
LROS (Lloyds register of shipping)
UKCA
Handle front plate colour 174 mm
Product or component type Contactor
tightening torque Control circuit: 1.2 N.m
Power circuit: 18 N.m
[uimp] rated impulse withstand voltage 8 kV
Connections - terminals Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm
Power circuit: lugs-ring terminals 1 cable(s) 150 mm²
Power circuit: connector 1 cable(s) 150 mm²
Power circuit: bolted connection
Associated fuse rating 200 A aM at <= 440 V
315 A gG at <= 440 V
Control circuit voltage limits Operational: 0.85...1.1 Uc (at 55 °C)
Drop-out: 0.15...0.2 Uc (at 55 °C)
width (w) 168.5 mm
Heat dissipation 5 W
Net weight 4.65 kg
Hold-in power consumption in w 5 W at 20 °C
Mounting support Plate
power dissipation per pole 12 W AC-3
25 W AC-1
depth 181 mm
inrush power in w 800 W (at 20 °C)
mechanical durability 10 Mcycles
Maximum operating rate 2400 cyc/h 55 °C
operating time 30...40 ms closing
30...50 ms opening
contactor coil voltage 110 V DC standard
Motor power range 30…50 kW at 200…240 V 3 phases
55…100 kW at 200…240 V 3 phases
55…100 kW at 380…440 V 3 phases
55…100 kW at 480…500 V 3 phases
110…220 kW at 480…500 V 3 phases
Power pole contact composition 3 NO
motor starter type Direct on-line contactor
Poles description 3P
Utilisation category AC-3
AC-1
AC-4
Environment
Ambient air temp for storage/transportation -60…80 °C
ip degree of protection IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106
operating altitude 3000 m without derating
Permissible ambient air temperature around the device -40…70 °C
Range of product TeSys F
ambient air temperature for operation -5…55 °C
overvoltage category III
standards EN 60947-4-1
JIS C8201-4-1
IEC 60947-4-1
EN 60947-1
IEC 60947-1
protective treatment TH
Recently viewed
919,67 €
919,67 € incl. VAT
Expected in 2-4 weeks