Main
Contactor application
Resistive load
Motor control
Device short name
LC1F
Range
TeSys
[uc] control circuit voltage
24 V AC 50 Hz
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
control circuit type
AC at 50 Hz
motor power kW
90 kW at 380...400 V AC 50/60 Hz (AC-3)
100 kW at 415 V AC 50/60 Hz (AC-3)
100 kW at 440 V AC 50/60 Hz (AC-3)
110 kW at 500 V AC 50/60 Hz (AC-3)
110 kW at 660...690 V AC 50/60 Hz (AC-3)
55 kW at 220...230 V AC 50/60 Hz (AC-3)
33 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0.33 mOhm - Ith 275 A 50 Hz
Complementary
[ie] rated operational current
275 A (at <40 °C) at <= 440 V AC-1
185 A (at <55 °C) at <= 440 V AC-3
[ue] rated operational voltage
<= 460 V DC
<= 690 V AC 50/60 Hz
compatibility code
LC1F
[ics] rated service breaking capacity
1480 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
1500 A 40 °C - 10 s
920 A 40 °C - 30 s
740 A 40 °C - 1 min
500 A 40 °C - 3 min
400 A 40 °C - 10 min
[ith] conventional thermal current
275 A (at 40 °C)
Product certifications
LROS (Lloyds register of shipping)
DNV
RMRoS
UL
RINA
CB
CCC
BV
ABS
UKCA
Handle front plate colour
174 mm
Product or component type
Contactor
tightening torque
Control circuit: 1.2 N.m
Power circuit: 18 N.m
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm
Power circuit: lugs-ring terminals 1 cable(s) 150 mm²
Power circuit: connector 1 cable(s) 150 mm²
Power circuit: bolted connection
Associated fuse rating
200 A aM at <= 440 V
315 A gG at <= 440 V
Control circuit voltage limits
Operational: 0.85...1.1 Uc 50/60 Hz (at 55 °C)
Drop-out: 0.35...0.55 Uc 50/60 Hz (at 55 °C)
width (w)
168.5 mm
Heat dissipation
18…24 W
Net weight
4.65 kg
Hold-in power consumption in va
55 VA, 50 Hz cos phi 0.3 (at 20 °C)
Mounting support
Plate
power dissipation per pole
12 W AC-3
25 W AC-1
depth
181 mm
Inrush power in va
805 VA, 50 Hz cos phi 0.3 (at 20 °C)
mechanical durability
10 Mcycles
Maximum operating rate
2400 cyc/h 55 °C
operating time
20...35 ms closing
7...15 ms opening
Power pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-3
AC-4
AC-1
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106
operating altitude
3000 m without derating
Permissible ambient air temperature around the device
-40…70 °C
Range of product
TeSys F
ambient air temperature for operation
-5…55 °C
overvoltage category
III
standards
JIS C8201-4-1
IEC 60947-4-1
EN 60947-4-1
EN 60947-1
IEC 60947-1
protective treatment
TH