Main
Contactor application
Motor control
Resistive load
Device short name
LC1F
Range
TeSys
[uc] control circuit voltage
48 V AC 40...400 Hz
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
control circuit type
AC at 40...400 Hz
motor power kW
75 kW at 380...400 V AC 50/60 Hz (AC-3)
80 kW at 415 V AC 50/60 Hz (AC-3)
80 kW at 440 V AC 50/60 Hz (AC-3)
90 kW at 500 V AC 50/60 Hz (AC-3)
100 kW at 660...690 V AC 50/60 Hz (AC-3)
40 kW at 220...230 V AC 50/60 Hz (AC-3)
22 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0.35 mOhm - Ith 250 A 50 Hz
Complementary
[ie] rated operational current
250 A (at <40 °C) at <= 440 V AC-1
150 A (at <55 °C) at <= 440 V AC-3
[ue] rated operational voltage
<= 690 V AC 50/60 Hz
<= 460 V DC
compatibility code
LC1F
[ics] rated service breaking capacity
1200 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
1200 A 40 °C - 10 s
700 A 40 °C - 30 s
600 A 40 °C - 1 min
450 A 40 °C - 3 min
350 A 40 °C - 10 min
[ith] conventional thermal current
250 A (at 40 °C)
Product certifications
RMRoS
DNV
BV
CCC
CB
RINA
ABS
LROS (Lloyds register of shipping)
UL
UKCA
Handle front plate colour
170 mm
Product or component type
Contactor
tightening torque
Control circuit: 1.2 N.m
Power circuit: 18 N.m
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) - busbar cross section: 25 x 3 mm
Power circuit: lugs-ring terminals 1 cable(s) 120 mm²
Power circuit: connector 1 cable(s) 120 mm²
Power circuit: bolted connection
Associated fuse rating
160 A aM at <= 440 V
250 A gG at <= 440 V
Control circuit voltage limits
Operational: 0.85...1.1 Uc 40...400 Hz (at 55 °C)
Drop-out: 0.2...0.55 Uc 40...400 Hz (at 55 °C)
width (w)
163.5 mm
Heat dissipation
5.9…7.2 W
Net weight
3.43 kg
Hold-in power consumption in va
8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
Mounting support
Plate
power dissipation per pole
22 W AC-1
8 W AC-3
depth
171 mm
Inrush power in va
770 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
mechanical durability
10 Mcycles
Maximum operating rate
2400 cyc/h 55 °C
operating time
35 ms closing (at Uc)
130 ms opening (at Uc)
Power pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-1
AC-4
AC-3
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106
operating altitude
3000 m without derating
Permissible ambient air temperature around the device
60…70 °C at Uc
Range of product
TeSys F
ambient air temperature for operation
-40…60 °C
overvoltage category
III
standards
EN 60947-1
EN 60947-4-1
IEC 60947-1
IEC 60947-4-1
JIS C8201-4-1
protective treatment
TH