Main
Contactor application
Resistive load
Motor control
Device short name
LC1F
Range
TeSys
[uc] control circuit voltage
220 V DC
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
control circuit type
DC standard
motor power kW
55 kW at 380...400 V AC 50/60 Hz (AC-3)
59 kW at 415 V AC 50/60 Hz (AC-3)
59 kW at 440 V AC 50/60 Hz (AC-3)
75 kW at 500 V AC 50/60 Hz (AC-3)
80 kW at 660...690 V AC 50/60 Hz (AC-3)
30 kW at 220...230 V AC 50/60 Hz (AC-3)
18.5 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0.37 mOhm - Ith 200 A 50 Hz
Complementary
[ie] rated operational current
200 A (at <40 °C) at <= 440 V AC-1
115 A (at <55 °C) at <= 440 V AC-3
[ue] rated operational voltage
<= 690 V AC 50/60 Hz
<= 460 V DC
compatibility code
LC1F
[ics] rated service breaking capacity
920 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
1100 A 40 °C - 10 s
640 A 40 °C - 30 s
520 A 40 °C - 1 min
400 A 40 °C - 3 min
320 A 40 °C - 10 min
[ith] conventional thermal current
200 A (at 40 °C)
Product certifications
BV
RINA
RMRoS
LROS (Lloyds register of shipping)
DNV
CB
UL
ABS
CCC
UKCA
Handle front plate colour
162 mm
Product or component type
Contactor
tightening torque
Power circuit: 10 N.m
Control circuit: 1.2 N.m
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Power circuit: bar 2 cable(s) - busbar cross section: 20 x 3 mm
Power circuit: lugs-ring terminals 1 cable(s) 95 mm²
Power circuit: connector 1 cable(s) 95 mm²
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bolted connection
Associated fuse rating
125 A aM at <= 440 V
200 A gG at <= 440 V
Control circuit voltage limits
Operational: 0.85...1.1 Uc (at 55 °C)
Drop-out: 0.15...0.2 Uc (at 55 °C)
width (w)
163.3 mm
Heat dissipation
4.5 W
Net weight
3.43 kg
Hold-in power consumption in w
4.5 W at 20 °C
Mounting support
Plate
power dissipation per pole
15 W AC-1
5 W AC-3
depth
171 mm
inrush power in w
560 W (at 20 °C)
mechanical durability
10 Mcycles
Maximum operating rate
2400 cyc/h 55 °C
operating time
30...40 ms closing
30...50 ms opening
Power pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-1
AC-3
AC-4
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106
operating altitude
3000 m without derating
Permissible ambient air temperature around the device
60…70 °C at Uc
Range of product
TeSys F
ambient air temperature for operation
-40…60 °C
overvoltage category
III
standards
JIS C8201-4-1
EN 60947-4-1
IEC 60947-4-1
EN 60947-1
IEC 60947-1
protective treatment
TH