Main
Contactor application
Resistive load
Motor control
Device short name
LC1F
Range
TeSys
[uc] control circuit voltage
24...575 V AC 40...400 Hz with LX9 coil
24...460 V DC with LX4 coil
100...250 V AC 50/60 Hz with LXE coil
100...380 V DC with LXE coil
Product Name
TeSys F
[ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
motor power kW
55 kW at 380...400 V AC 50/60 Hz (AC-3)
59 kW at 415 V AC 50/60 Hz (AC-3)
59 kW at 440 V AC 50/60 Hz (AC-3)
75 kW at 500 V AC 50/60 Hz (AC-3)
30 kW at 220...240 V AC 50/60 Hz (AC-3)
80 kW at 660...690 V AC 50/60 Hz (AC-3)
18.5 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0.37 mOhm - Ith 200 A 50 Hz
Complementary
[ie] rated operational current
200 A (at <40 °C) at <= 440 V AC-1
115 A (at <55 °C) at <= 440 V AC-3
[ue] rated operational voltage
<= 690 V AC 50/60 Hz
<= 460 V DC
compatibility code
LC1F
[ics] rated service breaking capacity
920 A conforming to IEC 60947-4-1
[icw] rated short-time withstand current
1100 A 40 °C - 10 s
640 A 40 °C - 30 s
520 A 40 °C - 1 min
400 A 40 °C - 3 min
320 A 40 °C - 10 min
[ith] conventional thermal current
200 A (at 40 °C)
Product certifications
RINA
ABS
CSA
DNV
RMRoS
BV
LROS (Lloyds register of shipping)
UL
CB
UKCA
Handle front plate colour
162 mm
Product or component type
Contactor
tightening torque
Power circuit: 10 N.m
Control circuit: 1.2 N.m
Control circuit: 0.6 N.m
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Power circuit: lugs-ring terminals 1 cable(s) 95 mm²
Power circuit: connector 1 cable(s) 95 mm²
Power circuit: bar 2 cable(s) - busbar cross section: 20 x 3 mm
Power circuit: bolted connection
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.25…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1.0 cable(s) 0.2…2.5 mm²solid without cable end
Associated fuse rating
125 A aM at <= 440 V
200 A gG at <= 440 V
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX9 coil
Drop-out: 0.2...0.55 Uc AC 40...400 Hz with LX9 coil
Operational: 0.85...1.1 Uc DC with LX4 coil
Drop-out: 0.15...0.2 Uc DC with LX4 coil
Operational: 85...275 V AC 50/60 Hz with LXE coil
Drop-out: 0...60 V AC 50/60 Hz with LXE coil
Operational: 85...418 V DC with LXE coil
Drop-out: 0...45 V DC with LXE coil
width (w)
163.5 mm
mechanical robustness
Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 6 Gn, 5...300 Hz
Shocks contactor open: 9 Gn for 1/2 sine wave (11 ms)
Shocks contactor closed: 15 Gn for 1/2 sine wave (11 ms)
Heat dissipation
5.9…7.2 W
2.2…5.5 W
Net weight
3.83 kg
Hold-in power consumption in va
6.6…8.1 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil
3.94…4.83 VA (at 20 °C)with LX4 coil
4.5…7.0 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
2.5…4.0 VA (at 20 °C)with LXE coil
Mounting support
Plate
power dissipation per pole
15 W AC-1
5 W AC-3
depth
171 mm
Inrush power in va
590…855 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX9 coil
543…665 VA (at 20 °C)with LX4 coil
280…310 VA, 50/60 Hz cos phi 0.5 (at 20 °C)with LXE coil
270…320 VA (at 20 °C)with LXE coil
mechanical durability
10 Mcycles
Irms rated making capacity
1150 A conforming to IEC 60947-4-1
Maximum operating rate
2400 cyc/h 55 °C
operating time
35 ms closing for with LX9 coil
130 ms opening for with LX9 coil
30...40 ms closing for with LX4 coil
30...50 ms opening for with LX4 coil
40...80 ms closing for with LXE coil
6...54 ms opening for with LXE coil
Power pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-1
AC-4
AC-3
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP2X front face with shrouds conforming to IEC 60529
IP2X front face with shrouds conforming to VDE 0106
operating altitude
3000 m without derating
Permissible ambient air temperature around the device
60…70 °C at Uc
ambient air temperature for operation
-40…60 °C
overvoltage category
III
standards
EN 60947-1
JIS C8201-4-1
IEC 60947-4-1
EN 60947-4-1
IEC 60947-1
protective treatment
TH