Main
Contactor application
Power factor correction
Device short name
LC1DLK
Device location in system
Inside delta interruption
Line interruption
Range
TeSys
TeSys Deca
[uc] control circuit voltage
230 V AC 50/60 Hz
Product Name
TeSys LC1D.K
TeSys Deca
Reactive power rating
11 kvar at 230 V AC 50 Hz 60 °C
20 kvar at 400 V AC 50 Hz 60 °C
21 kvar at 440 V AC 50 Hz 60 °C
33 kvar at 690 V AC 50 Hz 60 °C
control circuit type
AC at 50/60 Hz
Complementary
[ue] rated operational voltage
Power circuit: 690 V AC 50/60 Hz
Product certifications
IECEE CB Scheme
UKCA
Handle front plate colour
125 mm
Product or component type
Capacitor duty contactor
tightening torque
Control circuit: 1.7 N.m - on screw clamp terminals
Power circuit: 2.5 N.m - on screw clamp terminals
Auxiliary contact composition
1 NO + 2 NC instantaneous
Connections - terminals
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 2.5…16 mm² - cable stiffness: solid
Power circuit: screw clamp terminals 2 2.5…6 mm² - cable stiffness: solid
Power circuit: screw clamp terminals 1 1.5…10 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 1…10 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end
Auxiliary contacts type
type mechanically linked 1 NO + 2 NC conforming to IEC 60947-5-1
Device application
Control
width (w)
45 mm
Net weight
0.6 kg
Mounting support
DIN rail
Plate
depth
127 mm
electrical durability
300000 cycles at Ue 400 V
200000 cycles at Ue 690 V
Maximum operating rate
240 cyc/h
Power pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-6b
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP20 front face conforming to IEC 60529
operating altitude
0...3000 m
ambient air temperature for operation
-5…60 °C
standards
EN/IEC 60947-1
EN/IEC 60947-4-1
IEC 60335-1