All categories
Compare Cart

LC1D95V7 - TeSys Deca contactor 3P(3 NO) AC3/AC3e <= 440 V 95 A 400 V AC 50/60 Hz coil - Schneider Electric

Expected in 2-4 weeks
LC1D95V7 - TeSys Deca contactor 3P(3 NO) AC3/AC3e <= 440 V 95 A 400 V AC 50/60 Hz coil - Schneider Electric - TeSys Deca contactor 3P(3 NO) AC3/AC3e <= 440 V 95 A 400 V AC 50/60 Hz coil - Schneider Electric - 0
LC1D95V7 - TeSys Deca contactor 3P(3 NO) AC3/AC3e <= 440 V 95 A 400 V AC 50/60 Hz coil - Schneider Electric
258,00 €
258,00 € incl. VAT
Text About:
TeSys Deca contactor 3P(3 NO) AC3/AC3e <= 440 V 95 A 400 V AC 50/60 Hz coil - Schneider Electric
258,00 €
SPECIFICATIONS
Main
Contactor application Motor control
Resistive load
Device short name LC1D
Range TeSys
[uc] control circuit voltage 400 V AC 50/60 Hz
[ui] rated insulation voltage Power circuit: 1000 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
control circuit type AC at 50/60 Hz standard
motor power kW 25 kW at 220...230 V AC 50 Hz (AC-3)
45 kW at 380...400 V AC 50 Hz (AC-3)
45 kW at 415...440 V AC 50 Hz (AC-3)
55 kW at 500 V AC 50 Hz (AC-3)
45 kW at 660...690 V AC 50 Hz (AC-3)
15 kW at 400 V AC 50 Hz (AC-4)
25 kW at 220...230 V AC 50 Hz (AC-3e)
45 kW at 380...400 V AC 50 Hz (AC-3e)
45 kW at 415...440 V AC 50 Hz (AC-3e)
55 kW at 500 V AC 50 Hz (AC-3e)
45 kW at 660...690 V AC 50 Hz (AC-3e)
average impedance 0.8 mOhm - Ith 125 A 50 Hz for power circuit
Complementary
[ie] rated operational current 95 A (at <60 °C) at <= 440 V AC-3 for power circuit
125 A (at <60 °C) at <= 690 V AC-1 for power circuit
95 A (at <60 °C) at <= 440 V AC-3e for power circuit
[ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
compatibility code LC1D
[ics] rated service breaking capacity 1100 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current 1100 A 40 °C - 1 s for power circuit
800 A 40 °C - 10 s for power circuit
400 A 40 °C - 1 min for power circuit
135 A 40 °C - 10 min for power circuit
140 A - 100 ms for signalling circuit
120 A - 500 ms for signalling circuit
100 A - 1 s for signalling circuit
[ith] conventional thermal current 10 A (at 60 °C) for signalling circuit
125 A (at 60 °C) for power circuit
Product certifications IECEE CB Scheme
UL
CSA
CCC
EAC
LROS (Lloyds register of shipping)
RINA
BV
DNV-GL
Handle front plate colour 127 mm
Product or component type Contactor
tightening torque Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm
Power circuit: 12 N.m - on connector hexagonal screw head 4 mm
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
[uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947
Auxiliary contact composition 1 NO + 1 NC
Connections - terminals Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Power circuit: connector 1 4…50 mm² - cable stiffness: flexible without cable end
Power circuit: connector 2 4…25 mm² - cable stiffness: flexible without cable end
Power circuit: connector 1 4…50 mm² - cable stiffness: flexible with cable end
Power circuit: connector 2 4…16 mm² - cable stiffness: flexible with cable end
Power circuit: connector 1 4…50 mm² - cable stiffness: solid without cable end
Power circuit: connector 2 4…25 mm² - cable stiffness: solid without cable end
minimum switching current 5 mA for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
200 A gG at <= 690 V coordination type 1 for power circuit
160 A gG at <= 690 V coordination type 2 for power circuit
Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
contact compatibility M11
Control circuit voltage limits 0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
1...1.1 Uc (55…70 °C):operational AC 50/60 Hz
width (w) 85 mm
mechanical robustness Vibrations contactor open (2 Gn, 5...300 Hz)
Shocks contactor open (8 Gn for 11 ms)
Vibrations contactor closed (3 Gn, 5...300 Hz)
Shocks contactor closed (10 Gn for 11 ms)
Flame retardance V1 conforming to UL 94
Heat dissipation 6…10 W at 50/60 Hz
Net weight 1.61 kg
Hold-in power consumption in va 26 VA 60 Hz cos phi 0.3 (at 20 °C)
26 VA 50 Hz cos phi 0.3 (at 20 °C)
Motor power hp 7.5 hp at 120 V AC 60 Hz for 1 phase motors
15 hp at 230/240 V AC 60 Hz for 1 phase motors
30 hp at 200/208 V AC 60 Hz for 3 phases motors
30 hp at 230/240 V AC 60 Hz for 3 phases motors
60 hp at 460/480 V AC 60 Hz for 3 phases motors
60 hp at 575/600 V AC 60 Hz for 3 phases motors
Mounting support Plate
Rail
power dissipation per pole 12.5 W AC-1
7.2 W AC-3
7.2 W AC-3e
depth 130 mm
Inrush power in va 245 VA 60 Hz cos phi 0.75 (at 20 °C)
245 VA 50 Hz cos phi 0.75 (at 20 °C)
mechanical durability 4 Mcycles
electrical durability 1.2 Mcycles 95 A AC-3
1.3 Mcycles 125 A AC-1
1.2 Mcycles 95 A AC-3e
Irms rated making capacity 1100 A at 440 V AC for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Pollution degree 3
Maximum operating rate 3600 cyc/h 60 °C
operating time 20...35 ms closing
6...20 ms opening
minimum switching voltage 17 V for signalling circuit
non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Protective cover With
coil technology Without built-in suppressor module
Pole contact composition 3 NO
Poles description 3P
Utilisation category AC-3
AC-3e
AC-4
AC-1
Safety reliability level B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1
Signalling circuit frequency 25...400 Hz
Environment
Climatic withstand conforming to IACS E10 exposure to damp heat
ip degree of protection IP20 front face conforming to IEC 60529
operating altitude 0...3000 m
Permissible ambient air temperature around the device -40…60 °C
60…70 °C with derating
Range of product TeSys Deca
overvoltage category III
standards EN/IEC 60947-1
EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
fire resistance 850 °C conforming to IEC 60695-2-1
protective treatment TH conforming to IEC 60068-2-30
insulation resistance > 10 MOhm for signalling circuit
Recently viewed
258,00 €
258,00 € incl. VAT
Expected in 2-4 weeks