All categories
Compare Cart

LC1D098V7 - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil - Schneider Electric

Upon request only
LC1D098V7 - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil - Schneider Electric - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil - Schneider Electric - 0
LC1D098V7 - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil - Schneider Electric
Text About:
TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil - Schneider Electric
SPECIFICATIONS
Main
Contactor application Resistive load
Device short name LC1D
Range TeSys
[uc] control circuit voltage 400 V AC 50/60 Hz
[ui] rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
control circuit type AC at 50/60 Hz
average impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit
Complementary
[ie] rated operational current 20 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz
Power circuit: <= 300 V DC
compatibility code LC1D
[ics] rated service breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
[icw] rated short-time withstand current 105 A 40 °C - 10 s for power circuit
210 A 40 °C - 1 s for power circuit
30 A 40 °C - 10 min for power circuit
61 A 40 °C - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
[ith] conventional thermal current 25 A (at 60 °C) for power circuit
10 A (at 60 °C) for signalling circuit
Product certifications CSA
LROS (Lloyds register of shipping)
DNV
GL
GOST
UL
CCC
RINA
BV
Handle front plate colour 85 mm
Product or component type Contactor
tightening torque Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Auxiliary contact composition 1 NO + 1 NC
Connections - terminals Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
minimum switching current 5 mA for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
25 A gG at <= 690 V coordination type 1 for power circuit
20 A gG at <= 690 V coordination type 2 for power circuit
Auxiliary contacts type type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
contact compatibility M6
Control circuit voltage limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
width (w) 45 mm
mechanical robustness Vibrations contactor open (2 Gn, 5...300 Hz)
Vibrations contactor closed (4 Gn, 5...300 Hz)
Shocks contactor open (10 Gn for 11 ms)
Shocks contactor closed (15 Gn for 11 ms)
Flame retardance V1 conforming to UL 94
Heat dissipation 2…3 W at 50/60 Hz
Net weight 0.365 kg
Hold-in power consumption in va 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
Mounting support Rail
Plate
power dissipation per pole 1.56 W AC-1
depth 92 mm
Inrush power in va 70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
mechanical durability 15 Mcycles
electrical durability 0.6 Mcycles 25 A AC-1 at Ue <= 440 V
Irms rated making capacity 250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Pollution degree 3
Maximum operating rate 3600 cyc/h 60 °C
operating time 12...22 ms closing
4...19 ms opening
minimum switching voltage 17 V for signalling circuit
non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Protective cover With
coil technology Without built-in suppressor module
Pole contact composition 2 NO + 2 NC
Poles description 4P
Utilisation category AC-1
AC-3
AC-3e
AC-4
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Signalling circuit frequency 25...400 Hz
Environment
Climatic withstand conforming to IACS E10 exposure to damp heat
conforming to IEC 60947-1 Annex Q category D exposure to damp heat
ip degree of protection IP20 front face conforming to IEC 60529
operating altitude 0...3000 m
Permissible ambient air temperature around the device -40…60 °C
60…70 °C with derating
Range of product TeSys Deca
overvoltage category III
standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
fire resistance 850 °C conforming to IEC 60695-2-1
protective treatment TH conforming to IEC 60068-2-30
insulation resistance > 10 MOhm for signalling circuit
About this product

The LC1D098V7 - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil is developed to address the desires of trade professionals, such as switchboard fabricators, electrical fitters, upkeep firms, and original manufacturers. LC1D098V7 offers extraordinary durability and benefits for developers in the control systems industry. This TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil and other TeSyS Deca Contactors from Schneider Electric can be ordered at the lowest cost and shipping time through BaltElec online store, a credible distributor meeting the needs of contractors in their acquisition needs.

Consumers who have secured Schneider Electric TeSyS Deca Contactors have continuously praised the manufacturer’s soundness. It has been indicated that the excellent productivity of LC1D098V7 - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil extends to a variety of deployments. Its supreme attributes make it optimal for various requirements, assuring the success of your industrial, tertiary, and automation ventures.

Our professionals specializes in providing for industrial and tertiary professionals’ needs. We recognize the customized criteria and expectations of our patrons in the sector. By working with us, our customers gain access to the finest rates and availability of first-rate products like LC1D098V7 - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil from Schneider Electric at a reasonable price. Baltelec account members benefit from special savings and exclusive assistance.

Move quickly and obtain LC1D098V7 - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil at our certified and intuitive digital marketplace. Don't delay in making this prudent decision that ensures the supreme quality and caters to the targeted specifications of customers like you.

Should you experience any queries or concerns about LC1D098V7 - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil or any other Schneider Electric products, get in touch with us or refer to our FAQs section below. We have provided answers to routine problems to help you further in making an thoughtful decision about industrial and tertiary electrical components.

Remember, LC1D098V7 - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil from Schneider Electric is steady, reasonable, and premier to alternative suppliers in the TeSyS Deca Contactors category. Don't hesitate to make it a part of your installation today. Order at Baltelec webstore, your consistent provider for all your professional electrical equipment and automation needs.

In our Baltelec.eu electronic store you will identify TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil - LC1D098V7 worth 57.20 €, which will be a dependable and current solution for your needs. This goods is formulated by the Schneider Electric brand using the up-to-the-minute technologies and aligns with the pinnacle standards of guarding and effectiveness. We propose objects from the TeSyS Deca Contactors category that amalgamate durability and efficacy, which is an outstanding option for various objectives. Irrespective of whether you want devices for small production or for professional industrial employment, TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil will be a constant facilitator in your work.

Baltelec strives to make the getting process as uncomplicated and fast as achievable for our clients. We offer detailed explanations and high-quality portrayals of TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil so that you can make an advised choice. A team of maestros is always ready to help you with any inquiries in the TeSyS Deca Contactors section tied to the choice and use of wares. We are certain that TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil will meet your prospects and become an necessary element of your gear for just 57.20 €.

Frequently Asked Questions about LC1D098V7 - TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil:

Recently viewed
LC1D098V7 - Schneider Electric
TeSys Deca contactor - 4P(2 NO + 2 NC) - AC-1 - <= 440 V 20 A - 400 V AC coil
Upon request only