Main
Contacts operation
Time delay
Range
TeSys
TeSys Deca
Product Name
TeSys Deca
timer type
On delay
[ui] rated insulation voltage
690 V conforming to IEC 60947-5-1
600 V conforming to UL
600 V conforming to CSA
Complementary
[ie] rated operational current
6 A at 120 V AC-15
1.04 A at 690 V AC-15
0.55 A at 125 V DC-13
0.1 A at 600 V DC-13
[ue] rated operational voltage
690 V AC 25...400 Hz
range compatibility
TeSys D CAD
TeSys D LC1D
TeSys Deca CAD
TeSys Deca LC1D
[ith] conventional thermal current
10 A (at 60 °C)
Product certifications
CB
UL
CSA
CCC
EAC
UKCA
Handle front plate colour
48 mm
Product or component type
Time delay auxiliary contact block
mounting location
Front
Connections - terminals
Spring terminals 2 cable(s) 2.5 mm²flexible without cable end
Spring terminals 2 cable(s) 2.5 mm²rigid
minimum switching current
5 mA
width (w)
44 mm
Colour
Dark grey
depth
61 mm
mechanical durability
5 Mcycles
Irms rated making capacity
140 A AC
250 A DC
Permissible short-time rating
100 A 60 °C 1 s
120 A 60 °C 500 ms
140 A 60 °C 100 ms
Time delay range
1...30 s
minimum switching voltage
17 V
non-overlap time
1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact
Pole contact composition
1 NO + 1 NC
Protection type
GG fuse 10 A
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP2X conforming to IEC 60529
operating altitude
3000 m
ambient air temperature for operation
-40…70 °C
Environmental characteristics
Normal environment
standards
GB/T 14048.5
EN/IEC 60947-5-1
protective treatment
TH conforming to IEC 60068
insulation resistance
> 10 MOhm