Main
Contacts operation
Instantaneous
Device short name
LADN
Range
TeSys
TeSys Deca
Product Name
TeSys Deca
[ui] rated insulation voltage
690 V conforming to IEC 60947-5-1
600 V conforming to UL
600 V conforming to CSA
Complementary
[ie] rated operational current
6 A at 120 V AC-15
1.04 A at 690 V AC-15
0.55 A at 125 V DC-13
0.1 A at 600 V DC-13
[ue] rated operational voltage
690 V AC 25...400 Hz
range compatibility
TeSys D LC1D09...D80
TeSys D LC1DT20...DT40
TeSys D LC1DT60A...DT80A
TeSys F LC1F
TeSys F CR1F
TeSys Deca LC1D09...D80
TeSys Deca LC1DT20...DT40
TeSys Deca LC1DT60A...DT80A
[ith] conventional thermal current
10 A (at 60 °C)
Product certifications
CB
UL
CSA
CCC
EAC
UKCA
Handle front plate colour
48 mm
Product or component type
Auxiliary contact block
tightening torque
1.7 N.m - with screwdriver flat Ø 6 mm
1.7 N.m - with screwdriver Philips No 2
1.7 N.m - with screwdriver pozidriv No 2
mounting location
Front
Connections - terminals
Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end
minimum switching current
5 mA
width (w)
26 mm
Colour
Dark grey
depth
42 mm
mechanical durability
30 Mcycles
Irms rated making capacity
140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
Permissible short-time rating
100 A 60 °C 1 s
120 A 60 °C 500 ms
140 A 60 °C 100 ms
minimum switching voltage
17 V
non-overlap time
1.5 ms on de-energisation no overlap between NC and NO contact
1.5 ms on energisation no overlap between NC and NO contact
Pole contact composition
1 NO + 1 NC
Protection type
GG fuse 10 A
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
3000 m
ambient air temperature for operation
-5…60 °C
Environmental characteristics
Normal environment
standards
EN/IEC 60947-5-1
GB/T 14048.5
EN 50012
protective treatment
TH conforming to IEC 60068
insulation resistance
> 10 MOhm