Main
Device short name
LAD9
[ui] rated insulation voltage
750 V
Complementary
product compatibility
GV2ME direct on line
GV3P direct on line
[in] rated current
18 A per starter
60 A for power circuit conforming to IEC 60439-1
60 A per sub-base conforming to IEC 60439-1
[ue] rated operational voltage
690 V
[ics] rated service breaking capacity
50 kA at 415 V conforming to IEC 60439-1
[icw] rated short-time withstand current
9.1 kA for 70 ms conforming to IEC 60439-1
Product certifications
UL
CSA
Product or component type
Control connection module
[uimp] rated impulse withstand voltage
6 kV for power circuit
Connections - terminals
Control circuit: spring terminal 2 cable(s) 1.5 mm² flexible with cable end
Control circuit: spring terminal 2 cable(s) 2.5 mm² flexible
Control circuit: spring terminal 2 cable(s) 2.5 mm² solid
Power circuit: spring terminal 3 cable(s) 16 mm² flexible with cable end
Power circuit: spring terminal 3 cable(s) 25 mm² flexible
Power circuit: spring terminal 3 cable(s) 25 mm² solid
Derating factor
20 % of Imax GV2 circuit breaker 60 °C
mechanical robustness
Shocks 11 ms half sine wave acceleration (15 gn) conforming to IEC 60068-2-27
Vibrations 3...100 Hz (0.7 gn) conforming to BV
Vibrations 3...100 Hz (0.7 gn) conforming to IEC 60068-2-6
Vibrations 3...100 Hz (0.7 gn) conforming to LR
Vibrations 2...100 Hz (4 gn) conforming to BV
Vibrations 2...100 Hz (4 gn) conforming to IEC 60068-2-6
Vibrations 2...100 Hz (4 gn) conforming to LR
network frequency
50/60 Hz
Mounting mode
Fixed
Minimum clearance distance
30 mm
Mounting support
Mounting plate
2 x 35 mm symmetrical DIN rail
Pollution degree
3
Supply maximum power
0.36 W
Environment
Ambient air temp for storage/transportation
-40…70 °C
Climatic withstand
Resistance to incandescent wire: 960 °C conforming to IEC 60695-2-1
ip degree of protection
IP40
Range of product
TeSys D
ambient air temperature for operation
-5…40 °C wall mounted
-5…60 °C floor mounting
electromagnetic compatibility
Electrostatic discharge immunity test: , 3, conforming to IEC 61000-4-2
Fast transients immunity test: , 3, conforming to IEC 61000-4-4
Immunity to radiated fields: (26...1000 MHz), 10 V/m, conforming to IEC 61000-4-3
Radiated radio-frequency electromagnetic field immunity test: (0.15...80 MHz), 10 V, conforming to IEC 61000-4-6
Surge immunity test: (8...20 µs in differential mode), 0.6 kV, conforming to IEC 61000-4-5
Surge immunity test: (1.2...50 µs in common mode), 2 kV, conforming to IEC 61000-4-5
standards
IEC 60439-1