Main
Cam switch function
Reversing star-delta switch
Cam switch head type
With front plate 88 x 88 mm
Off position
With Off position
Presentation of legend
With metallic legend, delta - Y - 0 - Y - delta black marking
[ui] rated insulation voltage
690 V (pollution degree 3) conforming to EN/IEC 60947-1
Switching positions
Right: 0° - 45° - 90°
Left: 0° - 315° - 270°
component name
K115
Complementary
[ie] rated operational current ac
100 A AC-21A
[ith] conventional thermal current
115 A
Product certifications
CULus 120 V 5 hp 1 phase
CULus 240 V 10 hp 1 phase
CULus 240 V 20 hp 3 phases
CULus 480 V 30 hp 3 phases
Product or component type
Complete cam switch
tightening torque
2.5 N.m
[uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
mounting location
Front
switching angle
45 °
Cad overall depth
234 mm
Cad overall height
88 mm
contact operation
Slow-break
Fixing mode
4 holes
Cad overall width
88 mm
rated operational power in w
13000 W AC-3, 380/440 V 1 phase conforming to EN/IEC 60947-3
15000 W AC-23A, 220/240 V 1 phase conforming to EN/IEC 60947-3
15000 W AC-3, 220/240 V 3 phases conforming to EN/IEC 60947-3
22000 W AC-23A, 380/440 V 1 phase conforming to EN/IEC 60947-3
30000 W AC-23A, 220/240 V 3 phases conforming to EN/IEC 60947-3
30000 W AC-3, 380/440 V 3 phases conforming to EN/IEC 60947-3
30000 W AC-3, 660/690 V 3 phases conforming to EN/IEC 60947-3
3700 W AC-3, 110 V 1 phase conforming to EN/IEC 60947-3
45000 W AC-23A, 380/440 V 3 phases conforming to EN/IEC 60947-3
5500 W AC-23A, 110 V 1 phase conforming to EN/IEC 60947-3
65000 W AC-23A, 660/690 V 3 phases conforming to EN/IEC 60947-3
7500 W AC-3, 220/240 V 1 phase conforming to EN/IEC 60947-3
Rotary handle padlocking
Without
Type of operator
Black handle
Net weight
0.88 kg
switching capacity in ma
100000 mA DC at 140 V 3 contact(s) for resistive load (T = 1 ms)
100000 mA DC at 24 V 1 contact(s) for inductive load (T = 50 ms)
100000 mA DC at 48 V 1 contact(s) for resistive load (T = 1 ms)
100000 mA DC at 48 V 2 contact(s) for inductive load (T = 50 ms)
100000 mA DC at 70 V 3 contact(s) for inductive load (T = 50 ms)
100000 mA DC at 95 V 2 contact(s) for resistive load (T = 1 ms)
115000 mA DC at 24 V 1 contact(s) for resistive load (T = 1 ms)
115000 mA DC at 48 V 2 contact(s) for resistive load (T = 1 ms)
115000 mA DC at 70 V 3 contact(s) for resistive load (T = 1 ms)
33000 mA DC at 30 V 1 contact(s) for inductive load (T = 50 ms)
33000 mA DC at 60 V 2 contact(s) for inductive load (T = 50 ms)
33000 mA DC at 90 V 3 contact(s) for inductive load (T = 50 ms)
mechanical durability
300000 cycles
return
Without
Positive opening
With
electrical connection
Captive screw clamp terminals flexible, clamping capacity: 1 x 25 mm²
Captive screw clamp terminals solid, clamping capacity: 1 x 35 mm²
Short-circuit current
15000 A
Poles description
3P
Short-circuit protection
125 A cartridge fuse, type gG
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
IP40 conforming to IEC 529
IP40 conforming to NF C 20-010
Range of product
Harmony K
ambient air temperature for operation
-25…55 °C
overvoltage category
Class II conforming to IEC 60536
Class II conforming to NF C 20-030
standards
EN/IEC 60947-3
protective treatment
TC