Main
Device short name
IM10-H
Measurement current
0…0.2 mA
Range
Vigilohm
Measurement voltage
25 V
Earthing system
IT
threshold setting
Fault: 50...500 kOhm
Complementary
[ics] rated service breaking capacity
250 V - AC at 6 A
12...24 V - DC at 6 A
Product certifications
EAC
BV
CE
DNV
response time
<= 1 s
Handle front plate colour
110 mm
Product or component type
Insulation monitoring device
Connections - terminals
Removable screw terminal block0.2…2.5 mm²
Language
Italian
Spanish
Chinese
Russian
English
Portuguese
German
French
Network rated voltage
0…230 V - AC at 50/60 Hz (phase to neutral)
0…100 V - DC
Device application
Hospital
internal impedance
110 kOhm - AC at 50/60 Hz
type of measurement
Network insulation resistance - measurement range: 1 kOhm...10 MOhm
Material
Thermoplastic
width (w)
96 mm
Local signalling
Green indicator light: satisfactory insulation resistance
Orange indicator light: below fault threshold
Mounting mode
Flush-mounted
Clip-on
Net weight
0.25 kg
communication port protocol
-
Display type
Digital display
Mounting support
Panel
DIN rail
depth
59 mm
Pollution degree
2
Power consumption in va
12 VA
Type of installation
Indoor
auxiliary supply voltage
125...250 V DC +/- 15 %
110...230 V AC 50/60 Hz +/- 15 %
Output contact
1 C/O standard or fail-safe
Test function
Manual
dielectric strength
4000 V - AC
5500 V - DC
Environment
Ambient air temp for storage/transportation
-40…70 °C
ip degree of protection
Front face: IP52
ambient air temperature for operation
-25…55 °C
Environmental characteristics
Exposure to damp heat not in service conforming to IEC 60068-2-30
Exposure to damp heat in service conforming to IEC 60068-2-56
Salt mist conforming to IEC 60068-2-52
standards
IEC 61010-1
IEC 61557-8
IEC 60364-7-710
IEC 61326-2-4