Complementary
Product certifications
CE
UKCA
cULus
RCM
KC
cULus Class 1 Division 2
DNV
ABS
RINA
BV
Handle front plate colour
108.2 mm
Product or component type
Touch panel screen
[us] rated supply voltage
24 V DC (+/- 20 %)
inrush current
30 A
Cut-out dimensions
Ø 22,5 mm
marking
CE
Enclosure material
PC
processor frequency
800 MHz
Fixing mode
Ø 22 mm hole, mounting on 1.5 to 6 mm thick panel conforming to UL 61010-2-201
Ø 22 mm hole conforming to EN 61131-2
Ø 22 mm hole conforming to IEC 61000-6-2
width (w)
145.6 mm
Local signalling
Status LED green, steady for offline
Status LED green, steady for operating
Status LED green, flashing for operating
Status LED green, faded for stand-by
Status LED orange, flashing for software starting up
Status LED red, steady for power supply (ON)
Status LED red, flashing for operating
Status LED red, off for power supply (OFF)
Memory description
1 GB device memory
128 MB user data memory
512 kB backup memory
Net weight
0.27 kg
Realtime clock
Built-in 0...50 °C
Built-in 10...90 % RH
product brand
Schneider Electric Modicon
Mitsubishi Melsec
Omron Sysmac
Rockwell Automation Allen-Bradley
Siemens Simatic
Immunity to microbreaks
2 ms
Integrated connection type
1 COM1 serial link - female RJ45 - RS232C/RS485 (rate: 2400...115200 bps)bottom
1 USB 2.0 type Aback
1 USB 2.0 type micro Bback
2 Ethernet - female RJ45bottom
depth
41.4 mm
downloadable protocols
Modbus
Uni-TE
Third party protocols
Power consumption in w
6.8 W
software package
EcoStruxure Operator Terminal Expert
port ethernet
10/100BASE
Processor name
ARM Cortex-A8
Number of pages
200 application pages
Shock resistance
147 m/s² for 11 ms (X, Y, Z directions for 10 cycles (approx. 100 min)) conforming to EN/IEC 61131-2
Supply
External supply
Environment
Ambient air temp for storage/transportation
-20…60 °C
Directives
2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
ip degree of protection
IP20 (rear panel) conforming to IEC 61131-2
operating altitude
2000 m
Range of product
Harmony ST6
ambient air temperature for operation
0…50 °C
electromagnetic compatibility
Electrical fast transient/burst immunity test - test level: 2 kV (power ports) conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test - test level: 1 kV (signal ports)
Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2 level 3
Electrostatic discharge immunity test - test level: 8 kV (air discharge)
standards
EN 61000-6-4
EN 61000-6-2
EN 61131-2
UL 61010-2-201
CSA C22.2 No 61010-2-201
CSA C22.2 No 213
relative humidity
10…90 % non-condensing
vibration resistance
+/- 3.5 mm (f = 5…9 Hz) X, Y, Z directions for 10 cycles (approx. 100 min) conforming to EN/IEC 61131-2
9.8 m/s² (f = 9…150 Hz)