HHA080H - MCCB h3 x160 TM 3x80A 25kA - Hager - MCCB h3 x160 TM 3x80A 25kA - Hager - 0
HHA080H - MCCB h3 x160 TM 3x80A 25kA - Hager - MCCB h3 x160 TM 3x80A 25kA - Hager - 0
Pending restock

HHA080H – Hager

MCCB h3 x160 TM 3x80A 25kA - Hager
SPECIFICATIONS
Additional Information
type of order Toggle
type of pole 3P3D
Main
Number of modules 4.5
rated operational voltage ue 220 / 415 V
Complementary
air humidity protection for all climates
breaking capacity on 1 pole for it 230v nf 60947-2 21 kA
category of use A
complete device with protection unit Yes
connection cross-sect. flexible conductor 4 / 70mm²
correction factor of rating current for 2 devices placed side-by-side 1
din rail mounting with optional adaptator No
electric endurance in number of cycles 1000
magnetic trip delay time 0 ms
motor drive optional No
power loss per pole at in 10.7 W
range of the magnetic adjustment 1000 A
search words Compact circuit-breaker;Circuit-breaker;Main switch;Switch;Circuit-breaker;MCCB;
thermal protection trip time 0 ms
[in] rated current 80 A
breaking capacity on 1 pole for it 400v nf 60947-2 9 kA
connection cross-sect. rigid cable 4 / 95mm²
correction factor of rating current for 3 devices placed side-by-side 1
integrated earth fault protection No
number of mechanical operations 4000
setting type in or ith IN
time of response when opening 10 ms
total power loss under in 32.1 W
trip unit TM A/F
correction factor of rating current for 4 and 5 devices placed side-by-side 1
tripmode TM
type of connection with screw
with under voltage release No
correction factor of rating current for 6 devices placed side-by-side 1
rated service breaking capacity ics ac according iec 60947-2 80 %
storage/transport temperature -35…70 °C
rated ultimate short-circuit breaking capacity icu under 230v ac iec 60947-2 35 kA
Rated insulation voltage 690 V
rated ultimate short-circuit breaking capacity icu under 240v ac iec 60947-2 35 kA
connection Front connection
rated ultimate short-circuit breaking capacity icu under 400v ac iec 60947-2 25 kA
rated ultimate short-circuit breaking capacity icu under 415v ac iec 60947-2 25 kA
rated ultimate short-circuit breaking capacity icu under 440v ac iec 60947-2 20 kA
rated ultimate short-circuit breaking capacity icu under 690v ac iec 60947-2 4 kA
thermal protection nob setting xin 0.63 / 0.8 / 1
frequency 50/60
rated impulse withstand voltage 8 kV
Poles description 3 P
Environment
altitude 2000 m
european directive weee concerned
protection index ip IP4X
standard text IEC 60947-2
operating temperature -25…70 °C
Q&A and product info

Contact Us

Professional sales of electrical equipment in Estonia, Latvia, Lithuania, and Finland. Certified low-voltage components, circuit breakers, contactors, and industrial automation solutions. Same-day quotations and fast delivery across the Baltics and Finland.

Baltelec
+372 5326 4976

Mon–Fri 9:00–17:00

info@baltelec.eu

Response within 2 hours

HHA080H Hager is a professional Circuit Brakers product designed for professionals. BaltElec specializes in wholesale and supply in Estonia, Latvia, Lithuania, and Finland.

  • Authentic Hager product, documentation available on request.
  • Project pricing – request a quote for larger quantities (MOQ may apply).
  • Fast delivery across the Baltics and Finland; cooperation with trusted couriers.
  • Technical support and application suitability advice based on your requirements.

Price: Request a project quote. The price depends on quantity, delivery, and payment terms.

Circuit Brakers specifications may vary by model. For an exact match, please send us your requirements or check the technical data sheet.

FAQ for HHA080H - Hager

Recently viewed
HHA080H - Hager
MCCB h3 x160 TM 3x80A 25kA