Additional Information
type of order
Toggle
type of pole
4 P
Main
rated operational voltage ue
220 / 690 V
Neutral position
left
Complementary
air humidity protection
85% / 50°C
category of use
A
connection cross-sect. flexible conductor
2x240mm²
contact rating with 400 v in ac1
526 kW
correction factor of rating current for 2 devices placed side-by-side
1
electric endurance in number of cycles
4500
interlockable
Yes
motor drive optional
Yes
power loss per pole at in
49.6 W
reversing switch
No
search words
Switch disconnector;Load disconnecting switch;Main switch;Switch;Disconnector
toggle colour
Black
[in] rated current
800 A
connection cross-sect. rigid cable
2x240mm²
correction factor of rating current for 3 devices placed side-by-side
1
degree of pollution according to iec 60664 / iec 60947-2
3
number of mechanical operations
15000
rated operational current in ac21
800 A
time of response when opening
10 ms
total power loss under in
148.8 W
trip unit
SWITCH
correction factor of rating current for 4 and 5 devices placed side-by-side
1
type of connection
Terminal
correction factor of rating current for 6 devices placed side-by-side
1
storage/transport temperature
-35…70 °C
Rated insulation voltage
800 V
connection
Front connection
frequency
50/60
rated impulse withstand voltage
8 kV
Poles description
4 P
Environment
altitude
2000 m
european directive weee
concerned
protection index ip
IP4X
standard text
IEC 60947-3
operating temperature
-25…70 °C