Additional Information
type of order
Long thumb-grip
type of case
Fixed built-in
type of pole
4 P
Main
rated operational voltage ue
380 / 415 V
Complementary
acceptable current rating with ac22 category a
250 A
active power under 380/415 v, 50 hz
132 kW
contact rating with 400 v in ac1
164 kW
fixation type
Back plate monting
interlockable
Yes
motor drive integrated
No
motor drive optional
No
power loss per pole at in
5.8 W
reversing switch
No
search words
Switch disconnector;Load disconnecting switch;Main switch;Switch;Disconnector
[in] rated current
250 A
acceptable current rating with ac22 category b
250 A
connection cross-sect. rigid cable
150mm²
nominal power under 440/500, 50hz
140 kW
total power loss under in
17.4 W
width available for insulation connection
120
acceptable current rating with ac23 category b
200 A
nominal power under 660 v, 50 hz
90 kW
type of connection
Terminal
cut off current
30 kA
tightening torque
20
Rated insulation voltage
800 V
rated operational current in ac21 category a
250 A
rated operational current in ac21category b
250 A
rated operational current in ac23 category a
200 A
rated short-time withstand current 1s
9 kA
short-circuit current with gi-gg fuses
50 kA
rated impulse withstand voltage
8000 V
Poles description
4 P
Environment
european directive weee
concerned
protection index ip
IP00
standard text
IEC 60947-3
operating temperature
-20…70 °C