Additional Information
type of order
Long thumb-grip
type of case
Fixed built-in
type of pole
3 P
Main
rated operational voltage ue
380 / 415 V
Complementary
acceptable current rating with ac22 category a
160 A
connection cross-sect. flexible conductor
95mm²
contact rating with 400 v in ac1
105 kW
depth of installed product
120 mm
fixation type
Back plate monting
interlockable
Yes
motor drive integrated
No
motor drive optional
No
power loss per pole at in
3 W
reversing switch
No
search words
Switch disconnector;Load disconnecting switch;Main switch;Switch;Disconnector
[in] rated current
160 A
acceptable current rating with ac22 category b
160 A
connection cross-sect. rigid cable
95mm²
height of installed product
135 mm
nominal power under 440/500, 50hz
55 kW
total power loss under in
9 W
width available for insulation connection
95
acceptable current rating with ac23 category b
160 A
type of connection
Terminal
width of installed product
140 mm
cut off current
3.6 kA
Rated insulation voltage
800 V
rated operational current in ac21 category a
160 A
rated operational current in ac21category b
160 A
rated operational current in ac23 category a
160 A
rated short-time withstand current 1s
7 kA
short-circuit current with gi-gg fuses
50 kA
rated impulse withstand voltage
8000 V
Poles description
3 P
Environment
european directive weee
concerned
protection index ip
IP00
standard text
IEC 60947-3
operating temperature
-20…70 °C