Main
Device short name
GVAX
Range
TeSys
TeSys Deca
[uc] control circuit voltage
220...240 V AC 50 Hz
[ui] rated insulation voltage
690 V AC conforming to IEC 60947-1
600 V AC conforming to UL 60947-4-1
600 V AC conforming to CSA C22.2 No 60947-4-1
Complementary
range compatibility
TeSys GV2ME
TeSys Deca
Handle front plate colour
89 mm
Product or component type
Safety undervoltage trip
tightening torque
< 1.4 N.m on screw clamp terminals
Connections - terminals
Screw clamp terminals 1 cable(s) 1…2.5 mm²solid
Screw clamp terminals 2 cable(s) 1…2.5 mm²solid
Screw clamp terminals 1 cable(s) 0.75…2.5 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 0.75…2.5 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 0.75…1.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 0.75…1.5 mm²flexible with cable end
Quantity per set
Set of 10
Control circuit voltage limits
0.85...1.1 Un
width (w)
18 mm
On-load factor
100 %
Colour
Dark grey
Net weight
0.105 kg
Hold-in power consumption in va
3.5 VA AC
Hold-in power consumption in w
1.1 W
Threshold tripping voltage
0.7...0.35 Un
depth
66 mm
Inrush power in va
12 VA AC
inrush power in w
8 W
mechanical durability
30000 cycles
operating time
10...15 ms conforming to IEC 60947-1