Main
Device short name
GVAS
Range
TeSys
TeSys Deca
[uc] control circuit voltage
380...400 V AC 50 Hz
440 V AC 60 Hz
[ui] rated insulation voltage
690 V AC conforming to IEC 60947-1
600 V AC conforming to UL 60947-4-1
600 V AC conforming to CSA C22.2 No 60947-4-1
Complementary
range compatibility
TeSys GV2ME
TeSys GV2LE
TeSys GV2L
TeSys GV2P
TeSys GV3L
TeSys GV3P
TeSys Deca
Handle front plate colour
89 mm
Product or component type
Shunt trip release
tightening torque
< 1.4 N.m on screw clamp terminals
Connections - terminals
Screw clamp terminals 1 cable(s) 1…2.5 mm²solid
Screw clamp terminals 2 cable(s) 1…2.5 mm²solid
Screw clamp terminals 1 cable(s) 0.75…2.5 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 0.75…2.5 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 0.75…1.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 0.75…1.5 mm²flexible with cable end
Quantity per set
Set of 10
Control circuit voltage limits
0.7...1.1 Un
width (w)
18 mm
On-load factor
100 %
Colour
Dark grey
Net weight
0.105 kg
Hold-in power consumption in va
5 VA AC
Hold-in power consumption in w
1.6 W
Threshold tripping voltage
0.75...0.2 Un
depth
66 mm
Inrush power in va
14 VA AC
inrush power in w
10.5 W
mechanical durability
10000 cycles with GV3P and GV3L
30000 cycles with GV2ME and GV2P
operating time
10...15 ms conforming to IEC 60947-1