Main
Range
TeSys
name of the device
GV7AE
type of product or equipment
Bloc de contact auxiliaire
[ui] rated insulation voltage
690 V se conformer à CEI 60947-1
operation of auxiliary contacts
Instantané
Complementary
[ie] rated operational current
6 A AC-12 Ue: <= 690 V se conformer à CEI 60947-5-1
6 A AC-15 Ue: <= 48 V se conformer à CEI 60947-5-1
5 A AC-15 Ue: 110...127 V se conformer à CEI 60947-5-1
4 A AC-15 Ue: 230...240 V se conformer à CEI 60947-5-1
3 A AC-15 Ue: 380...440 V se conformer à CEI 60947-5-1
0,1 A AC-15 Ue: 660...690 V se conformer à CEI 60947-5-1
2,5 A DC-12 Ue: <= 48 V se conformer à CEI 60947-5-1
0,8 A DC-12 Ue: 110 V se conformer à CEI 60947-5-1
0,3 A DC-12 Ue: 250 V se conformer à CEI 60947-5-1
1 A DC-14 Ue: <= 24 V se conformer à CEI 60947-5-1
0,5 A DC-14 Ue: 48 V se conformer à CEI 60947-5-1
0,2 A DC-14 Ue: 110 V se conformer à CEI 60947-5-1
0,05 A DC-14 Ue: 250 V se conformer à CEI 60947-5-1
[ue] rated operational voltage
<= 690 V CA 50/60 Hz
<= 250 V CC
application
Signalisation
range compatibility
TeSys (TeSys GV5) disjoncteur moteur
TeSys (TeSys GV6) disjoncteur moteur
TeSys (TeSys GV7) disjoncteur moteur
[ith] conventional thermal current
6 A se conformer à CEI 60947-5-1
auxiliary contacts
1 "OF"
mounting location
À l'intérieur du disjoncteur
minimum switching current
5 mA
product weight
0,015 kg
type of auxiliary contacts
Contacts standards
connection mode
Borniers à vis-étrier 1 câble(s) 1,5 mm²souple avec extrémité de câble
Borniers à vis-étrier 1 câble(s) 1,5 mm²souple sans extrémité de câble
Borniers à vis-étrier 1 câble(s) 1,5 mm²rigide
mechanical endurance
50000 cycle
minimum switching voltage
17 V
kind of protection
Fusible gG 10 A maximum
GB2CB…disjoncteur 10 A maximum