Main
Device short name
GV7AB
Range
TeSys
[ui] rated insulation voltage
690 V conforming to IEC 60947-1
Complementary
[ie] rated operational current
5 A AC-12 Ue: <= 690 V conforming to IEC 60947-5-1
5 A AC-15 Ue: <= 48 V conforming to IEC 60947-5-1
4 A AC-15 Ue: 110...127 V conforming to IEC 60947-5-1
3 A AC-15 Ue: 230...240 V conforming to IEC 60947-5-1
2.5 A AC-15 Ue: 380...440 V conforming to IEC 60947-5-1
0.1 A AC-15 Ue: 660...690 V conforming to IEC 60947-5-1
2 A DC-12 Ue: <= 48 V conforming to IEC 60947-5-1
0.5 A DC-12 Ue: 110 V conforming to IEC 60947-5-1
0.5 A DC-14 Ue: <= 24 V conforming to IEC 60947-5-1
0.25 A DC-14 Ue: 48 V conforming to IEC 60947-5-1
0.1 A DC-14 Ue: 110 V conforming to IEC 60947-5-1
[ue] rated operational voltage
<= 690 V AC 50/60 Hz
<= 110 V DC
range compatibility
TeSys (TeSys GV5) motor circuit breaker
TeSys (TeSys GV6) motor circuit breaker
TeSys (TeSys GV7) motor circuit breaker
[ith] conventional thermal current
6 A conforming to IEC 60947-5-1
Auxiliary contacts operation
Instantaneous
Product or component type
Auxiliary contact block
Auxiliary contact composition
1 C/O
mounting location
Inside the circuit breaker
Connections - terminals
Screw clamps terminals 1 cable(s) 1.5 mm²flexible with cable end
Screw clamps terminals 1 cable(s) 1.5 mm²flexible without cable end
Screw clamps terminals 1 cable(s) 1.5 mm²rigid
minimum switching current
5 mA
Auxiliary contacts type
Low level contacts
Device application
Signalling
Net weight
0.015 kg
mechanical durability
50000 cycles
minimum switching voltage
12 V
Protection type
GG fuse 10 A maximum
GB2CB... circuit breaker 10 A maximum