All categories
Compare Cart

GV6P500H - Motor circuit breaker, TeSys GV6, 3P, 500A, Icu 70kA, thermal magnetic - Schneider Electric

Expected in 2-4 weeks
GV6P500H - Motor circuit breaker, TeSys GV6, 3P, 500A, Icu 70kA, thermal magnetic - Schneider Electric - Motor circuit breaker, TeSys GV6, 3P, 500A, Icu 70kA, thermal magnetic - Schneider Electric - 0
GV6P500H - Motor circuit breaker, TeSys GV6, 3P, 500A, Icu 70kA, thermal magnetic - Schneider Electric
1 404,06 € excl. VAT
1 712,95 € incl. VAT
Text About:
Motor circuit breaker, TeSys GV6, 3P, 500A, Icu 70kA, thermal magnetic - Schneider Electric
1 712,95 €
SPECIFICATIONS
Main
Device short name GV6P
Range TeSys
magnetic tripping current 6500 A
Product Name TeSys GV6
TeSys Giga
Trip unit technology Electronic
[ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
motor power kW 200…250 kW at 400/415 V AC 50/60 Hz
250…315 kW at 500 V AC 50/60 Hz
315…400 kW at 660/690 V AC 50/60 Hz
Complementary
[in] rated current 500 A at 65 °C
[ue] rated operational voltage 690 V AC 50/60 Hz
[ics] rated service breaking capacity 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[ith] conventional thermal current 500 A conforming to IEC 60947-4-1
Control type Direct rotary handle
Product certifications IECEE CB Scheme
EAC (pending)
Connection pitch 45 mm without spreaders
Handle front plate colour 255 mm
Product or component type Motor circuit breaker
tightening torque 50 N.m M10 screw type
[uimp] rated impulse withstand voltage 8 kV
Connections - terminals Bars
Lugs
Device application Motor protection
width (w) 140 mm
mechanical robustness Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
Colour Anthracite (RAL 7016)
Ik degree of protection IK07 conforming to IEC 62262
Net weight 6.7 kg
power dissipation per pole 39.7 W
depth 179 mm
mechanical durability 15000 cycles
electrical durability 4000 cycles for AC-3 at 400/415 V In
Maximum operating rate 25 cyc/h
Phase failure sensitivity Yes conforming to IEC 60947-4-1
Rated duty Continuous
Suitability for isolation Yes conforming to EN/IEC 60947-2
Poles description 3P
Utilisation category Category A conforming to IEC 60947-2
Environment
Ambient air temp for storage/transportation -50…85 °C
Climatic withstand conforming to IACS E10
ip degree of protection IP40 conforming to IEC 60529
operating altitude 5000 m
Range of product TeSys GV6
ambient air temperature for operation -25…70 °C
standards EN/IEC 60947-1
EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
fire resistance 960 °C conforming to IEC 60695-2-11
Recently viewed
1 404,06 € excl. VAT
1 712,95 € incl. VAT