Main
Device short name
GV5P
Range
TeSys
magnetic tripping current
3300 A
Product Name
TeSys GV5
TeSys Giga
Trip unit technology
Electronic
[ui] rated insulation voltage
800 V AC 50/60 Hz conforming to IEC 60947-2
motor power kW
90…110 kW at 400/415 V AC 50/60 Hz
110 kW at 500 V AC 50/60 Hz
110…132 kW at 660/690 V AC 50/60 Hz
Complementary
[in] rated current
220 A at 65 °C
[ue] rated operational voltage
690 V AC 50/60 Hz
[ics] rated service breaking capacity
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[ith] conventional thermal current
220 A conforming to IEC 60947-4-1
Control type
Direct rotary handle
Product certifications
IECEE CB Scheme
EAC (pending)
Connection pitch
35 mm without spreaders
Handle front plate colour
161 mm
Product or component type
Motor circuit breaker
tightening torque
15 N.m M8 screw type
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Bars
Lugs
Device application
Motor protection
width (w)
105 mm
mechanical robustness
Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
Colour
Anthracite (RAL 7016)
Ik degree of protection
IK07 conforming to IEC 62262
Net weight
2.6 kg
power dissipation per pole
17.6 W
depth
155 mm
mechanical durability
20000 cycles
electrical durability
10000 cycles for AC-3 at 400/415 V In
Maximum operating rate
25 cyc/h
Phase failure sensitivity
Yes conforming to IEC 60947-4-1
Rated duty
Continuous
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Poles description
3P
Utilisation category
Category A conforming to IEC 60947-2
Environment
Ambient air temp for storage/transportation
-50…85 °C
Climatic withstand
conforming to IACS E10
ip degree of protection
IP40 conforming to IEC 60529
operating altitude
5000 m
Range of product
TeSys GV5
ambient air temperature for operation
-25…70 °C
standards
EN/IEC 60947-1
EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
fire resistance
960 °C conforming to IEC 60695-2-11