Main
																					
												Device short name
												GV4PE
											
                            
																					
												Range
												TeSys Deca
TeSys Deca
											
                            
																					
												magnetic tripping current
												1360 A
											
                            
																					
												Product Name
												TeSys GV4
TeSys Deca
											
                            
																					
												Trip unit technology
												Thermal-magnetic
Electronic
											
                            
																					
												[ui] rated insulation voltage
												800 V AC 50/60 Hz conforming to IEC 60947-2
											
                            
																					
												motor power kW
												37 kW at 400...415 V AC 50/60 Hz
45 kW at 500 V AC 50/60 Hz
22 kW at 400...415 V AC 50/60 Hz
30 kW at 500 V AC 50/60 Hz
37 kW at 660...690 V AC 50/60 Hz
45 kW at 660...690 V AC 50/60 Hz
55 kW at 660...690 V AC 50/60 Hz
30 kW at 400...415 V AC 50/60 Hz
37 kW at 500 V AC 50/60 Hz
											
                            
																			 
																	
										Complementary
																					
												[in] rated current
												80 A
											
                            
																					
												[ue] rated operational voltage
												690 V AC 50/60 Hz conforming to IEC 60947-2
											
                            
																					
												[ics] rated service breaking capacity
												100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947
65 kA at 240 V AC 50/60 Hz conforming to UL 60947
35 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947
8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
18 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947
											
                            
																					
												[ith] conventional thermal current
												115 A conforming to IEC 60947-4-1
											
                            
																					
												Control type
												Toggle
											
                            
																					
												Product certifications
												IEC
UL
CSA
CCC
EAC
ATEX
EU-RO MR
											
                            
																					
												Handle front plate colour
												155 mm
											
                            
																					
												Product or component type
												Motor circuit breaker
											
                            
																					
												tightening torque
												9 N.m for cable 16…95 mm²
5 N.m for cable 1.5…10 mm²
											
                            
																					
												[uimp] rated impulse withstand voltage
												8 kV conforming to IEC 60947-2
											
                            
																					
												Connections - terminals
												EverLink BTR screw connectors (top) 1 cable(s) 1.5…70 mm² - solid
EverLink BTR screw connectors (top) 1 cable(s) 1.5…50 mm² - flexible
EverLink BTR screw connectors (bottom) 1 cable(s) 2.5…95 mm² - solid
EverLink BTR screw connectors (bottom) 1 cable(s) 2.5…70 mm² - flexible
											
                            
																					
												Device application
												Motor protection
											
                            
																					
												width (w)
												81 mm
											
                            
																					
												mechanical robustness
												Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
Shocks: 15 gn 11 ms conforming to IEC 60068-2-27
											
                            
																					
												Colour
												Grey (RAL 7016)
											
                            
																					
												Ik degree of protection
												IK07 conforming to IEC 62262
											
                            
																					
												Net weight
												1.45 kg
											
                            
																					
												Operating position
												Any position
											
                            
																					
												power dissipation per pole
												4.6 W
											
                            
																					
												depth
												116 mm
											
                            
																					
												mechanical durability
												40000 cycles
											
                            
																					
												electrical durability
												14000 cycles for AC-3 at 440 V In/2
7000 cycles for AC-3 at 440 V In
											
                            
																					
												Pollution degree
												3
											
                            
																					
												Maximum operating rate
												25 cyc/h
											
                            
																					
												Phase failure sensitivity
												Yes conforming to IEC 60947-4-1
											
                            
																					
												Rated duty
												Continuous conforming to IEC 60947-4-1
											
                            
																					
												Suitability for isolation
												Yes conforming to IEC 60947-1
											
                            
																					
												Poles description
												3P
											
                            
																					
												Utilisation category
												Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
											
                            
																			 
																	
										Environment
																					
												Ambient air temp for storage/transportation
												-50…85 °C
											
                            
																					
												Climatic withstand
												conforming to IACS E10
											
                            
																					
												ip degree of protection
												IP40 conforming to IEC 60529
											
                            
																					
												operating altitude
												5000 m
											
                            
																					
												Range of product
												TeSys GV4
											
                            
																					
												ambient air temperature for operation
												-25…70 °C
											
                            
																					
												standards
												CSA C22.2 No 60947-4-1
UL 60947-4-1
EN/IEC 60947-4-1
EN/IEC 60947-2
											
                            
																					
												fire resistance
												960 °C conforming to IEC 60695-2-11