Main
Device short name
GV4L
Range
TeSys Deca
TeSys Deca
magnetic tripping current
42…98 A
Product Name
TeSys GV4
TeSys Deca
Trip unit technology
Magnetic
Electronic
[ui] rated insulation voltage
800 V AC 50/60 Hz conforming to IEC 60947-2
motor power kW
1.5 kW at 400...415 V AC 50/60 Hz
2.2 kW at 400...415 V AC 50/60 Hz
2.5 kW at 400...415 V AC 50/60 Hz
3 kW at 400...415 V AC 50/60 Hz
2.2 kW at 500 V AC 50/60 Hz
2.5 kW at 500 V AC 50/60 Hz
3 kW at 500 V AC 50/60 Hz
4 kW at 500 V AC 50/60 Hz
3 kW at 660...690 V AC 50/60 Hz
4 kW at 660...690 V AC 50/60 Hz
5.5 kW at 660...690 V AC 50/60 Hz
7.5 kW at 660...690 V AC 50/60 Hz
Complementary
[in] rated current
7 A
[ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[ics] rated service breaking capacity
120 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[ith] conventional thermal current
115 A conforming to IEC 60947-4-1
Control type
Toggle
Product certifications
IEC
CCC
EAC
EU-RO MR
Connection pitch
27 mm without spreaders
35 mm with spreaders
Handle front plate colour
155 mm
Product or component type
Motor circuit breaker
tightening torque
9 N.m for cable 16…95 mm²
5 N.m for cable 1.5…10 mm²
[uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947-2
Connections - terminals
Lugs-ring terminals
Device application
Motor protection
width (w)
81 mm
mechanical robustness
Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
Shocks: 15 gn 11 ms conforming to IEC 60068-2-27
Colour
Grey (RAL 7016)
Ik degree of protection
IK07 conforming to IEC 62262
Net weight
1.5 kg
Operating position
Any position
power dissipation per pole
6.1 W
depth
116 mm
mechanical durability
40000 cycles
electrical durability
40000 cycles for AC-3 at 440 V In/2
40000 cycles for AC-3 at 440 V In
Pollution degree
3
Maximum operating rate
25 cyc/h
Rated duty
Continuous conforming to IEC 60947-4-1
Suitability for isolation
Yes conforming to IEC 60947-1
Poles description
3P
Utilisation category
Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
Environment
Ambient air temp for storage/transportation
-50…85 °C
Climatic withstand
conforming to IACS E10
ip degree of protection
IP40 conforming to IEC 60529
operating altitude
5000 m
Range of product
TeSys GV4
ambient air temperature for operation
-25…70 °C
standards
EN/IEC 60947-4-1
EN/IEC 60947-2
fire resistance
960 °C conforming to IEC 60695-2-11