All categories
Compare Cart

GV4L25N - Motor circuit breaker, TeSys GV4, 3P, 25 A, Icu 50 kA, magnetic, EverLink terminals - Schneider Electric

In stock
GV4L25N - Motor circuit breaker, TeSys GV4, 3P, 25 A, Icu 50 kA, magnetic, EverLink terminals - Schneider Electric - Motor circuit breaker, TeSys GV4, 3P, 25 A, Icu 50 kA, magnetic, EverLink terminals - Schneider Electric - 0
GV4L25N - Motor circuit breaker, TeSys GV4, 3P, 25 A, Icu 50 kA, magnetic, EverLink terminals - Schneider Electric
232,16 € excl. VAT
287,88 € incl. VAT
Text About:
Motor circuit breaker, TeSys GV4, 3P, 25 A, Icu 50 kA, magnetic, EverLink terminals - Schneider Electric
287,88 €
SPECIFICATIONS
Main
Device short name GV4L
Range TeSys Deca
TeSys Deca
magnetic tripping current 150…350 A
Product Name TeSys GV4
TeSys Deca
Trip unit technology Magnetic
Electronic
[ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
motor power kW 7.5 kW at 660...690 V AC 50/60 Hz
5.5 kW at 400...415 V AC 50/60 Hz
7.5 kW at 500 V AC 50/60 Hz
9 kW at 660...690 V AC 50/60 Hz
11 kW at 660...690 V AC 50/60 Hz
7.5 kW at 400...415 V AC 50/60 Hz
9 kW at 400...415 V AC 50/60 Hz
11 kW at 400...415 V AC 50/60 Hz
9 kW at 500 V AC 50/60 Hz
11 kW at 500 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660...690 V AC 50/60 Hz
18.5 kW at 660...690 V AC 50/60 Hz
Complementary
[in] rated current 25 A
[ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[ics] rated service breaking capacity 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[ith] conventional thermal current 115 A conforming to IEC 60947-4-1
Control type Rotary handle
Product certifications IEC
CCC
EAC
EU-RO MR
Handle front plate colour 155 mm
Product or component type Motor circuit breaker
tightening torque 9 N.m for cable 16…95 mm²
5 N.m for cable 1.5…10 mm²
[uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
Connections - terminals EverLink BTR screw connectors (top) 1 cable(s) 1.5…70 mm² - solid
EverLink BTR screw connectors (top) 1 cable(s) 1.5…50 mm² - flexible
EverLink BTR screw connectors (bottom) 1 cable(s) 2.5…95 mm² - solid
EverLink BTR screw connectors (bottom) 1 cable(s) 2.5…70 mm² - flexible
Device application Motor protection
width (w) 81 mm
mechanical robustness Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
Shocks: 15 gn 11 ms conforming to IEC 60068-2-27
Colour Grey (RAL 7016)
Ik degree of protection IK07 conforming to IEC 62262
Net weight 1.65 kg
Operating position Any position
power dissipation per pole 6.1 W
depth 165 mm
mechanical durability 40000 cycles
electrical durability 40000 cycles for AC-3 at 440 V In/2
20000 cycles for AC-3 at 440 V In
Pollution degree 3
Maximum operating rate 25 cyc/h
Rated duty Continuous conforming to IEC 60947-4-1
Suitability for isolation Yes conforming to IEC 60947-1
Poles description 3P
Utilisation category Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
Environment
Ambient air temp for storage/transportation -50…85 °C
Climatic withstand conforming to IACS E10
ip degree of protection IP40 conforming to IEC 60529
operating altitude 5000 m
Range of product TeSys GV4
ambient air temperature for operation -25…70 °C
standards EN/IEC 60947-4-1
EN/IEC 60947-2
fire resistance 960 °C conforming to IEC 60695-2-11
Q&A and product info

Contact Us

Professional sales of electrical equipment in Estonia, Latvia, Lithuania, and Finland. Certified low-voltage components, circuit breakers, contactors, and industrial automation solutions. Same-day quotations and fast delivery across the Baltics and Finland.

Baltelec
+372 5326 4976

Mon–Fri 9:00–17:00

info@baltelec.eu

Response within 2 hours

GV4L25N is a professional TeSyS Deca GV4 Motor Circuit Breaker product designed for professionals. BaltElec specializes in wholesale and product distribution in Estonia, Latvia, Lithuania, and Finland.

  • Authentic Schneider Electric product, certificates and compliance documents available.
  • Project pricing – request a quote for larger quantities (MOQ may apply).
  • Fast delivery across the Baltics and Finland; cooperation with trusted couriers.
  • Technical support and application suitability advice based on your requirements.

Pricing: Request a project quote. The price depends on quantity, delivery, and payment terms.

TeSyS Deca GV4 Motor Circuit Breaker specifications may vary by model. For an exact match, please send us your application details or check the technical data sheet.

FAQ for GV4L25N - Schneider Electric

Recently viewed
GV4L25N - Schneider Electric
Motor circuit breaker, TeSys GV4, 3P, 25 A, Icu 50 kA, magnetic, EverLink terminals
232,16 € excl. VAT
287,88 € incl. VAT
In stock