Main
Device short name
GV3L
Range
TeSys Deca
magnetic tripping current
448 A
Product Name
TeSys GV3
TeSys Deca
Trip unit technology
Magnetic
[ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
motor power kW
15 kW at 400/415 V AC 50/60 Hz
18.5 kW at 500 V AC 50/60 Hz
22 kW at 690 V AC 50/60 Hz
Complementary
[in] rated current
32 A
[ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[ics] rated service breaking capacity
100 % at 230/240 V AC 50/60 Hz
100 % at 400/415 V AC 50/60 Hz
100 % at 440 V AC 50/60 Hz
50 % at 500 V AC 50/60 Hz
50 % at 690 V AC 50/60 Hz
Control type
Rotary handle
Product certifications
CCC
UL
CSA
EAC
LROS (Lloyds register of shipping)
BV
ABS
DNV-GL
UKCA
Handle front plate colour
132 mm
Product or component type
Motor circuit breaker
tightening torque
5 N.m - on screw clamp terminal
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Device application
Motor protection
Fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)
width (w)
55 mm
mechanical robustness
Shocks: 15 Gn for 11 ms contactor open
Shocks: 30 Gn for 11 ms contactor closed
Vibrations: 4 Gn, 5...300 Hz
network frequency
50/60 Hz
Colour
Dark grey
Net weight
0.96 kg
power dissipation per pole
8 W
depth
136 mm
mechanical durability
50000 cycles
electrical durability
50000 cycles for AC-3 at 415 V In
Network type
AC
Suitability for isolation
Yes conforming to IEC 60947-1
Poles description
3P
Utilisation category
Category A conforming to IEC 60947-2
Environment
Ambient air temp for storage/transportation
-40…80 °C
Climatic withstand
conforming to IACS E10
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
3000 m
ambient air temperature for operation
-20…60 °C
standards
EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
fire resistance
960 °C conforming to IEC 60695-2-11