All categories
Compare Cart

GV2RT163 - Motor circuit breaker,TeSys Deca,3P,9-14A,thermal magnetic,spring terminals,toggle handle - Schneider Electric

Expected in 2-4 weeks
GV2RT163 - Motor circuit breaker,TeSys Deca,3P,9-14A,thermal magnetic,spring terminals,toggle handle - Schneider Electric - Motor circuit breaker,TeSys Deca,3P,9-14A,thermal magnetic,spring terminals,toggle handle - Schneider Electric - 0
GV2RT163 - Motor circuit breaker,TeSys Deca,3P,9-14A,thermal magnetic,spring terminals,toggle handle - Schneider Electric
138,80 €
138,80 € incl. VAT
Text About:
Motor circuit breaker,TeSys Deca,3P,9-14A,thermal magnetic,spring terminals,toggle handle - Schneider Electric
138,80 €
SPECIFICATIONS
Main
Device short name GV2RT
Range TeSys Deca
magnetic tripping current 280 A
Product Name TeSys GV2
TeSys Deca
Trip unit technology Thermal-magnetic
[ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
thermal protection adjustment range 9…14 A conforming to IEC 60947-4-1
motor power kW 2.2 kW at 220/230 V AC 50/60 Hz motor protection high peak current
3 kW at 220/230 V AC 50/60 Hz motor protection high peak current
5.5 kW at 400/415 V AC 50/60 Hz motor protection high peak current
5.5 kW at 440 V AC 50/60 Hz motor protection high peak current
7.5 kW at 440 V AC 50/60 Hz motor protection high peak current
7.5 kW at 500 V AC 50/60 Hz motor protection high peak current
9 kW at 690 V AC 50/60 Hz motor protection high peak current
11 kW at 690 V AC 50/60 Hz motor protection high peak current
4 kW at 230/240 V AC 50/60 Hz transformer protection
6.3 kW at 400/415 V AC 50/60 Hz transformer protection
10 kW at 690 V AC 50/60 Hz transformer protection
12.5 kW at 690 V AC 50/60 Hz transformer protection
Complementary
[in] rated current 14 A
[ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[ics] rated service breaking capacity 100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[ith] conventional thermal current 14 A conforming to IEC 60947-4-1
Control type Toggle
Product certifications CCC
UL
CSA
EAC
LROS (Lloyds register of shipping)
BV
UKCA
Handle front plate colour 89 mm
Product or component type Motor circuit breaker
[uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
Device application Motor protection
Transformer
Fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
width (w) 45 mm
mechanical robustness Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hz
network frequency 50/60 Hz conforming to IEC 60947-4-1
Ik degree of protection IK04
power dissipation per pole 2.5 W
depth 78.5 mm
mechanical durability 100000 cycles
electrical durability 100000 cycles for AC-3 at 415 V In
Network type AC
Rated duty Continuous conforming to IEC 60947-4-1
Suitability for isolation Yes conforming to IEC 60947-1 § 7-1-6
Poles description 3P
Utilisation category Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
Environment
Ambient air temp for storage/transportation -40…80 °C
Climatic withstand conforming to IACS E10
ip degree of protection IP20 conforming to IEC 60529
operating altitude 2000 m
ambient air temperature for operation -20…60 °C
standards EN/IEC 60947-2
EN/IEC 60947-4-1
fire resistance 960 °C conforming to IEC 60695-2-11
Recently viewed
138,80 €
138,80 € incl. VAT
Expected in 2-4 weeks