Main
Device short name
GV2RT
Range
TeSys Deca
magnetic tripping current
138 A
Product Name
TeSys GV2
TeSys Deca
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
thermal protection adjustment range
4…6.3 A conforming to IEC 60947-4-1
motor power kW
1.1 kW at 220/230 V AC 50/60 Hz motor protection high peak current
2.2 kW at 400/415 V AC 50/60 Hz motor protection high peak current
2.2 kW at 440 V AC 50/60 Hz motor protection high peak current
3 kW at 440 V AC 50/60 Hz motor protection high peak current
3 kW at 500 V AC 50/60 Hz motor protection high peak current
4 kW at 690 V AC 50/60 Hz motor protection high peak current
1.6 kW at 230/240 V AC 50/60 Hz transformer protection
2 kW at 230/240 V AC 50/60 Hz transformer protection
2.5 kW at 400/415 V AC 50/60 Hz transformer protection
2.5 kW at 440 V AC 50/60 Hz transformer protection
4 kW at 440 V AC 50/60 Hz transformer protection
4 kW at 500 V AC 50/60 Hz transformer protection
4 kW at 690 V AC 50/60 Hz transformer protection
5 kW at 690 V AC 50/60 Hz transformer protection
6.3 kW at 690 V AC 50/60 Hz transformer protection
Complementary
[in] rated current
6.3 A
[ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[ics] rated service breaking capacity
100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[ith] conventional thermal current
6.3 A conforming to IEC 60947-4-1
Control type
Toggle
Product certifications
CCC
UL
CSA
EAC
LROS (Lloyds register of shipping)
BV
UKCA
Handle front plate colour
89 mm
Product or component type
Motor circuit breaker
tightening torque
1.7 N.m - on screw clamp terminal
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Device application
Motor protection
Transformer
Fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
width (w)
45 mm
mechanical robustness
Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hz
network frequency
50/60 Hz conforming to IEC 60947-4-1
Ik degree of protection
IK04
power dissipation per pole
2.5 W
depth
78.5 mm
mechanical durability
100000 cycles
electrical durability
100000 cycles for AC-3 at 415 V In
Network type
AC
Rated duty
Continuous conforming to IEC 60947-4-1
Suitability for isolation
Yes conforming to IEC 60947-1 § 7-1-6
Poles description
3P
Utilisation category
Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
Environment
Ambient air temp for storage/transportation
-40…80 °C
Climatic withstand
conforming to IACS E10
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
2000 m
ambient air temperature for operation
-20…60 °C
standards
EN/IEC 60947-2
EN/IEC 60947-4-1
fire resistance
960 °C conforming to IEC 60695-2-11