Main
Device short name
GV2ME
Range
TeSys Deca
magnetic tripping current
8 A
Product Name
TeSys GV2
TeSys Deca
Trip unit technology
Thermal-magnetic
[ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
thermal protection adjustment range
0.4…63 A conforming to IEC 60947-4-1
motor power kW
0.12 kW at 400/415 V AC 50/60 Hz
0.18 kW at 400/415 V AC 50/60 Hz
Complementary
[in] rated current
0.63 A
[ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[ics] rated service breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
[ith] conventional thermal current
0.63 A conforming to IEC 60947-4-1
Control type
Push-button
Product certifications
CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCA
Handle front plate colour
101 mm
Product or component type
Motor circuit breaker
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Device application
Motor protection
Fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
width (w)
45 mm
mechanical robustness
Shocks: 30 Gn for 11 ms
Vibrations: 5 Gn, 5...150 Hz
network frequency
50/60 Hz conforming to IEC 60947-4-1
Colour
Dark grey
Ik degree of protection
IK04
Net weight
0.28 kg
power dissipation per pole
2.5 W
depth
78.5 mm
mechanical durability
100000 cycles
electrical durability
100000 cycles for AC-3 at 415 V In
Network type
AC
Phase failure sensitivity
Yes conforming to IEC 60947-4-1
Rated duty
Continuous conforming to IEC 60947-4-1
Suitability for isolation
Yes conforming to IEC 60947-1 § 7-1-6
Poles description
3P
Utilisation category
Category A conforming to IEC 60947-2
AC-3 conforming to IEC 60947-4-1
Environment
Ambient air temp for storage/transportation
-40…80 °C
Climatic withstand
conforming to IACS E10
ip degree of protection
IP20 conforming to IEC 60529
operating altitude
2000 m
ambient air temperature for operation
-20…60 °C
standards
EN/IEC 60947-2
EN/IEC 60947-4-1
fire resistance
960 °C conforming to IEC 60695-2-11