Complementary
acceptable current load with ac7 category a
40 A
can be accessorized
Yes
command voltage ac
230 V
connection cross-sect. flexible conductor
1,5 / 16mm²
contact rating with 230 v in ac7 category a
7.3 kW
depth of installed product
60 mm
electric endurance in number of cycles
30000
fluorescent lamps in duo circuit
3000 VA
inrush power absorbed
62.5 VA
local operation/hand operation
No
max. power with fluorescent parallel lamps
1300 VA
max. power with incandescent lamps
4000 W
search words
Installation contactor;Mini contactor;Rail mounted device;Contactor;Control contactor;AC contactor;
time of response when closing
25 ms
winding resistance
770 Ω
[in] rated current
40 A
acceptable current load with ac7 category b
25 A
connection cross-sect. rigid cable
1,5 / 25mm²
contact rating with 230 v in ac7 category b
2.6 kW
dc control voltage
0 V
height of installed product
85 mm
max. load fluorescent lamp
1900 VA
number of mechanical operations
1000000
time of response when opening
20 ms
total power loss under in
11.1 W
connection cross-section of the control cable solid
1 / 2.5 mm²
contact rating with 400 v in ac7 category a
22 kW
number of contacts
3
type of connection
with screw
width of installed product
54 mm
contact rating with 400 v in ac7 category b
7.8 kW
operating consumption
5.7 VA
storage/transport temperature
-40…80 °C
thermal rated current outside of housings
40 A
tightening torque
Coil: 2,5Nm ; Power: 3,5Nm
power dissipation per coil
1.5 W
type of contacts
3NO
power loss per contact
3.2 W
Rated insulation voltage
440 V
frequency
50
rated impulse withstand voltage
4 kV
Poles description
3 P