Main
Coil type
Standard
Device short name
CR1F
Range
TeSys
[uc] control circuit voltage
380 V AC 50/60 Hz
Product Name
TeSys F
[ui] rated insulation voltage
Control circuit: 1000 V conforming to BS 775
Control circuit: 1000 V conforming to IEC 60158-1
Control circuit: 1000 V conforming to IEC 60947-4
Control circuit: 1500 V conforming to VDE 0110 group C
average impedance
0.28 Ohm - Ith 500 A 50 Hz for control circuit
Complementary
average consumption
12 VA AC 50/60 Hz unlatching
1450 VA AC 50/60 Hz latching
[ie] rated operational current
370 A (at <40 °C) AC/DC AC-4 for power circuit
400 A (at <40 °C) AC/DC AC-3 for power circuit
500 A (at <40 °C) AC/DC AC-1 for power circuit
[ue] rated operational voltage
Power circuit: 1000 V AC
Power circuit: 1000 V DC
[ics] rated service breaking capacity
1200 A at 1000 V for power circuit
3000 A at 600...690 V for power circuit
3500 A at 500 V for power circuit
4000 A at 220...440 V for power circuit
[ith] conventional thermal current
500 A (at 40 °C) for power circuit
Product certifications
CB Scheme
UL
CSA
EAC
CE
UKCA
Handle front plate colour
375 mm
Product or component type
Magnetic contactor
Connections - terminals
Bolted connection
Associated fuse rating
400 A aM for power circuit
500 A BS88 for power circuit
500 A gG for power circuit
Quantity per set
Set of 10
Control circuit voltage limits
Latching: 0.85...1.1 Uc
Unlatching: 0.85...1.1 Uc
width (w)
261 mm
Net weight
9.1 kg
Operating position
+/- 5°
power dissipation per pole
70 W AC-1
66 W AC-4
66 W AC-3
depth
219 mm
mechanical durability
1000000 cycles
Irms rated making capacity
4500 A for power circuit
Maximum operating rate
120 cyc/mn 40 °C
operating time
40...75 ms latching
50...100 ms unlatching
Power pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-4
AC-1
AC-3
Environment
operating altitude
3000 m without derating
ambient air temperature for operation
-15…70 °C
standards
EN/IEC 60947-1
EN/IEC 60947-4-1
JIS C8201-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
protective treatment
TH