Main
Contactor application
Resistive load
Motor control
Device short name
CR1F
Range
TeSys
[uc] control circuit voltage
220...230 V AC 50...400 Hz
220...230 V DC
Product Name
TeSys F
[ui] rated insulation voltage
1000 V conforming to IEC 60158-1
1000 V conforming to IEC 60947-4
1000 V conforming to BS 775
1500 V conforming to VDE 0110 group C
control circuit type
AC at 50...400 Hz
DC standard
motor power kW
75 kW at 400 V AC 50/60 Hz (AC-4)
average impedance
0.45 mOhm - Ith 250 A 50 Hz
Complementary
average consumption
1260 VA AC 50...400 Hz latching
10 VA AC 50...400 Hz unlatching
1260 VA DC latching
10 VA DC unlatching
[ie] rated operational current
150 A (at <40 °C) at <= 440 V AC AC-3
250 A (at <40 °C) at <= 440 V AC AC-1
138 A (at <40 °C) at <= 440 V AC AC-4
[ue] rated operational voltage
1000 V AC 25...200 Hz
[ics] rated service breaking capacity
1500 A at 220...440 V
1200 A at 500 V
450 A at 1000 V
1100 A at 660/690 V
[icw] rated short-time withstand current
1200 A 40 °C - 1 s
1200 A 40 °C - 5 s
1200 A 40 °C - 10 s
700 A 40 °C - 30 s
600 A 40 °C - 1 min
450 A 40 °C - 3 min
350 A 40 °C - 10 min
Product certifications
CB Scheme
UL
CSA
EAC
CE
UKCA
Handle front plate colour
170 mm
Product or component type
Magnetic latching contactor
tightening torque
18 N.m
Connections - terminals
Lugs-ring terminals 1 cable(s) 120 mm²
Connector 1 cable(s) 120 mm²
Bars 2 cable(s) - busbar cross section: 25 x 3 mm
Power circuit: bolted connection
Associated fuse rating
160 A aM at <= 440 V
250 A BS88 at <= 440 V
250 A gG at <= 440 V
Device application
Control
Control circuit voltage limits
Latching: 0.85...1.1 Uc
Unlatching: 0.85...1.1 Uc
width (w)
163.5 mm
Net weight
3.5 kg
power dissipation per pole
6 W AC-3
18 W AC-1
depth
171 mm
mechanical durability
1 Mcycles
Irms rated making capacity
1700 A
Maximum operating rate
120 cyc/h 40 °C
operating time
35...40 ms latching
50...100 ms unlatching
Power pole contact composition
3 NO
Poles description
3P
Utilisation category
AC-3
AC-1
AC-4
Environment
Ambient air temp for storage/transportation
-60…80 °C
operating altitude
3000 m without derating
ambient air temperature for operation
-15…70 °C
standards
EN/IEC 60947-1
EN/IEC 60947-4-1
JIS C8201-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
protective treatment
TC