Main
Device short name
IC2000
number of channels
1
Product Name
Acti9 IC
Complementary
9 mm pitches
5
electrical insulation class
Class II
[ue] rated operational voltage
230 V AC +10 % -15 % at 50/60 Hz
compatibility code
IC2000
Control type
By brightness detection
maximum switching current
10 A - 250 V AC pf = 0.6
16 A - 250 V AC pf = 1
Brightness sensing type
Analog wall-mounted cell
Handle front plate colour
85 mm
Product or component type
Twilight switch
market segment
Residential
Small commercial
opening distance
< 3 mm
Connections - terminals
2 x 2.5 mm² screwless terminals
Device application
Building
width (w)
45 mm
function available
Cabling test function with a push-button on front face
Net weight
280 g
depth
65 mm
light intensity adjustment
2…2000 lux
Load type
230 V AC halogen lamp: 2300 W
230 V AC incandescent lamp: 2300 W
dual mounted fluorescent tube with conventional ballast: 2300 VA
dual mounted fluorescent tube with electronic ballast: 300 VA
fluocompact lamp with conventional ballast: 1500 VA
non-corrected fluorescent tube with conventional ballast: 2300 VA
parallel-corrected fluorescent tube with conventional ballast: 400 VA
parallel-corrected mercury and sodium vapour lamps: 400 VA
serial-corrected fluorescent tube with conventional ballast: 2300 VA
7 x 11 W fluocompact lamp with electronic ballast
7 x 15 W fluocompact lamp with electronic ballast
7 x 20 W fluocompact lamp with electronic ballast
7 x 23 W fluocompact lamp with electronic ballast
9 x 7 W fluocompact lamp with electronic ballast
Power consumption in va
6 VA
Provided equipment
wall-mounted cell
Status led
LED (green) threshold reached
LED (red) brightness less than the threshold
Time delay
>= 60 s on closing
>= 60 s on breaking contact
Environment
ip degree of protection
IP20 B
Range of product
Acti9
ambient air temperature for operation
-25…50 °C
standards
EN 60529
EN 60669