Main
Device short name
IC100k
number of channels
1
Product Name
Acti9 IC
Complementary
9 mm pitches
4
electrical insulation class
Class II
[ue] rated operational voltage
230 V AC +10 % -15 % at 50/60 Hz
compatibility code
IC100k
Control type
By brightness detection
maximum switching current
10 A - 250 V AC pf = 0.6
16 A - 250 V AC pf = 1
Brightness sensing type
Digital wall-mounted cell
Handle front plate colour
90 mm
Product or component type
Twilight switch
market segment
Residential
Small commercial
Connections - terminals
2 x 2.5 mm² screwless terminals
Language
Romanian
Hungarian
Polish
Czech
Slovene
Bulgarian
Slovak
Spanish
Serbian
English
Croatian
French
Greek
Portuguese
Device application
Building
width (w)
36 mm
Net weight
183 g
depth
69 mm
light intensity adjustment
1…99000 lux
Load type
230 V AC halogen lamp: 2600 W
230 V AC incandescent lamp: 2600 W
parallel-corrected mercury and sodium vapour lamps: 800 VA
26 x 36 W non-corrected fluorescent tube with conventional ballast
20 x 58 W non-corrected fluorescent tube with conventional ballast
10 x 100 W non-corrected fluorescent tube with conventional ballast
26 x 36 W serial-corrected fluorescent tube with conventional ballast
20 x 58 W serial-corrected fluorescent tube with conventional ballast
10 x 100 W serial-corrected fluorescent tube with conventional ballast
26 x 36 W dual mounted fluorescent tube with conventional ballast
20 x 58 W dual mounted fluorescent tube with conventional ballast
10 x 100 W dual mounted fluorescent tube with conventional ballast
10 x 36 W parallel-corrected fluorescent tube with conventional ballast
6 x 58 W parallel-corrected fluorescent tube with conventional ballast
2 x 100 W parallel-corrected fluorescent tube with conventional ballast
18 x 11 W fluocompact lamp with electronic ballast
16 x 15 W fluocompact lamp with electronic ballast
16 x 20 W fluocompact lamp with electronic ballast
14 x 23 W fluocompact lamp with electronic ballast
22 x 7 W fluocompact lamp with electronic ballast
motor: 2300 VA
fluorescent tube with electronic ballast: 650 VA
Power consumption in va
3 VA
Provided equipment
digital switchboard cell
programming kit for PC
digital wall-mounted cell
Time delay
< 60 s
Environment
ip degree of protection
IP20C
Range of product
Acti9
ambient air temperature for operation
-30…50 °C
standards
EN 60529