All categories
Compare Cart
HEF980H - MCCB h1600 3P 70kA 1250A LSI - Hager - MCCB h1600 3P 70kA 1250A LSI - Hager - 0
HEF980H - MCCB h1600 3P 70kA 1250A LSI - Hager - MCCB h1600 3P 70kA 1250A LSI - Hager - 0
Pending restock

HEF980H – Hager

MCCB h1600 3P 70kA 1250A LSI - Hager
SPECIFICATIONS
Additional Information
type of order Toggle
type of pole 3P3D
Main
Number of modules 12
rated operational voltage ue 220 / 690 V
Complementary
air humidity protection for all climates
breaking capacity on 1 pole for it 230v nf 60947-2 60 kA
category of use A
complete device with protection unit Yes
connection cross-sect. flexible conductor 3x240mm²
correction factor of rating current for 2 devices placed side-by-side 1
din rail mounting with optional adaptator No
electric endurance in number of cycles 1000
magnetic protection nob setting xin 2.5 / 5 / 10
magnetic trip delay time 100 to 200 ms
motor drive optional Yes
power loss per pole at in 62.5 W
range of the magnetic adjustment 7000 / 8750 / 11200 / 14000 / 15000 / 15000 / 15000 A
search words Compact circuit-breaker;Circuit-breaker;Main switch;Switch;Circuit-breaker;MCCB;
thermal protection trip time 5 / 10 / 11 / 19 / 21 / 29 ms
[in] rated current 1250 A
breaking capacity on 1 pole for it 400v nf 60947-2 9 kA
connection cross-sect. rigid cable 3x240mm²
correction factor of rating current for 3 devices placed side-by-side 1
integrated earth fault protection No
number of mechanical operations 4000
setting type in or ith IrTh
time of response when opening 10 ms
total power loss under in 187.5 W
trip unit LSI
correction factor of rating current for 4 and 5 devices placed side-by-side 1
tripmode LSI
type of connection Terminal
with under voltage release No
correction factor of rating current for 6 devices placed side-by-side 1
rated service breaking capacity ics ac according iec 60947-2 71 %
storage/transport temperature -35…70 °C
rated ultimate short-circuit breaking capacity icu under 230v ac iec 60947-2 100 kA
Rated insulation voltage 800 V
rated ultimate short-circuit breaking capacity icu under 240v ac iec 60947-2 100 kA
connection Front connection
rated ultimate short-circuit breaking capacity icu under 400v ac iec 60947-2 70 kA
rated ultimate short-circuit breaking capacity icu under 415v ac iec 60947-2 70 kA
rated ultimate short-circuit breaking capacity icu under 440v ac iec 60947-2 70 kA
rated ultimate short-circuit breaking capacity icu under 690v ac iec 60947-2 45 kA
thermal protection nob setting xin 0.4 / 0.5 / 0.63 / 0.8 / 0.9 / 0.95 / 1
frequency 50/60
rated impulse withstand voltage 8 kV
Poles description 3 P
Environment
altitude 2000 m
european directive weee concerned
protection index ip IP4X
standard text IEC 60947-2
operating temperature -25…70 °C
Q&A and product info

Contact Us

Professional sales of electrical equipment in Estonia, Latvia, Lithuania, and Finland. Certified low-voltage components, circuit breakers, contactors, and industrial automation solutions. Same-day quotations and fast delivery across the Baltics and Finland.

Baltelec
+372 5326 4976

Mon–Fri 9:00–17:00

info@baltelec.eu

Response within 2 hours

HEF980H is a professional Circuit Brakers product designed for professionals. BaltElec specializes in wholesale and product distribution in Estonia, Latvia, Lithuania, and Finland.

  • Authentic Hager product, documentation available on request.
  • Volume-based pricing – request a quote for larger quantities (MOQ may apply).
  • Fast delivery across the Baltics and Finland; cooperation with logistics partners.
  • Technical support and application suitability advice based on your requirements.

Pricing: Request a project quote. The price depends on quantity, delivery, and payment terms.

Circuit Brakers specifications may vary by configuration. For an exact match, please send us your application details or check the technical data sheet.

FAQ for HEF980H - Hager

Recently viewed
HEF980H - Hager
MCCB h1600 3P 70kA 1250A LSI
Pending restock