Complementary
[ue] rated operational voltage
<= 690 V <= 400 Hz
[icw] rated short-time withstand current
90 A 50 °C - 1 s
85 A 50 °C - 5 s
80 A 50 °C - 10 s
60 A 50 °C - 30 s
45 A 50 °C - 1 min
40 A 50 °C - 3 min
20 A 50 °C - >= 15 min
[ith] conventional thermal current
20 A (at 50 °C)
Product certifications
CB Scheme
CCC
UL
CSA
EAC
CE
UKCA
Handle front plate colour
58 mm
Product or component type
Control relay
tightening torque
Power circuit: 1.1 N.m - on lugs-ring terminals - with screwdriver Philips No 23.2 mm
Power circuit: 1.1 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm3.2 mm
Power circuit: 1.1 N.m - on lugs-ring terminals - with screwdriver pozidriv No 2
[uimp] rated impulse withstand voltage
8 kV
Connections - terminals
Lugs-ring terminals (external diameter: 7 mm)
minimum switching current
5 mA
Associated fuse rating
10 A gG conforming to IEC 60947
10 A gG conforming to VDE 0660
Control circuit voltage limits
Operational: 0.7...1.3 Uc (at <50 °C)
Drop-out: <= 0.1 Uc (at <50 °C)
width (w)
45 mm
mechanical robustness
Vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27
Flame retardance
V0 conforming to UL 94
Heat dissipation
1.8 W
Net weight
0.235 kg
Hold-in power consumption in w
1.8 W at 20 °C
Immunity to microbreaks
2 ms
Mounting support
Plate
Rail
depth
57 mm
inrush power in w
1.8 W (at 20 °C)
mechanical durability
30 Mcycles
Irms rated making capacity
110 A at 690 V conforming to IEC 60947
110 A at 690 V conforming to NF C 63-110
Maximum operating rate
6000 cyc/h
operating time
10...20 ms coil de-energisation and NO opening
15...25 ms coil de-energisation and NC closing
30...40 ms coil energisation and NO closing
25...35 ms coil energisation and NC opening
minimum switching voltage
17 V
Non overlap distance
0.5 mm
coil technology
With integral suppression device
Pole contact composition
3 NO + 1 NC
Poles description
4P
Utilisation category
DC-13
AC-15
Environment
Ambient air temp for storage/transportation
-50…80 °C
ip degree of protection
IP20 conforming to VDE 0106
operating altitude
2000 m without derating
ambient air temperature for operation
-25…50 °C
standards
BS 5424
IEC 60947
VDE 0660
IEC 60077-1
IEC 60077-2
EN 45545: R22 HL3
NF C 63-110
EN/IEC 60947-5-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
protective treatment
TC conforming to IEC 60068
TC conforming to DIN 50016
insulation resistance
> 10 MOhm