Main
Contactor application
Control circuit
Device short name
CAD
Range
TeSys
TeSys Deca
[uc] control circuit voltage
440 V AC 50/60 Hz
Product Name
TeSys CAD
[ui] rated insulation voltage
600 V UL certified
600 V CSA certified
690 V conforming to IEC 60947-5-1
control circuit type
AC at 50/60 Hz
Complementary
[ue] rated operational voltage
<= 690 V AC 25...400 Hz
[icw] rated short-time withstand current
100 A - 1 s
120 A - 500 ms
140 A - 100 ms
[ith] conventional thermal current
10 A (at 60 °C)
Product certifications
CB Scheme
CCC
UL
CSA
EAC
CE
UKCA
Handle front plate colour
77 mm
Product or component type
Control relay
tightening torque
1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
Connections - terminals
Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
minimum switching current
5 mA
Associated fuse rating
10 A gG conforming to IEC 60947-5-1
Control circuit voltage limits
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
width (w)
45 mm
mechanical robustness
Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Net weight
0.58 kg
Hold-in power consumption in va
8 VA 50 Hz (at 20 °C)
Mounting support
Rail
Plate
depth
84 mm
Inrush power in va
70 VA 50 Hz (at 20 °C)
mechanical durability
30 Mcycles
Irms rated making capacity
140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
Maximum operating rate
180 cyc/mn
operating time
12...22 ms coil energisation and NO closing
4...12 ms coil de-energisation and NO opening
4...19 ms coil energisation and NC opening
6...17 ms coil de-energisation and NC closing
minimum switching voltage
17 V
non-overlap time
1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
Pole contact composition
3 NO + 2 NC
Utilisation category
AC-15
AC-14
DC-13
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP2X front face conforming to VDE 0106
operating altitude
0...3000 m
ambient air temperature for operation
-40…60 °C
60…70 °C with derating
standards
EN/IEC 60947-5-1
GB/T 14048.5
UL 60947-5-1
CSA C22.2 No 60947-5-1
JIS C8201-5-1
protective treatment
TH conforming to IEC 60068
insulation resistance
> 10 MOhm