Main
Contactor application
Control circuit
Device short name
CAD
Range
TeSys
TeSys Deca
[uc] control circuit voltage
24 V DC
Product Name
TeSys CAD
[ui] rated insulation voltage
600 V UL certified
600 V CSA certified
690 V conforming to IEC 60947-5-1
control circuit type
DC standard
Complementary
[ue] rated operational voltage
<= 690 V AC 25...400 Hz
[icw] rated short-time withstand current
100 A - 1 s
120 A - 500 ms
140 A - 100 ms
[ith] conventional thermal current
10 A (at 60 °C)
Product certifications
CB Scheme
CCC
UL
CSA
EAC
CE
UKCA
Handle front plate colour
99 mm
Product or component type
Control relay
[uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947
Connections - terminals
Spring terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Spring terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Spring terminals 1 cable(s) 1…2.5 mm²solid without cable end
Spring terminals 2 cable(s) 1…2.5 mm²solid without cable end
minimum switching current
5 mA
Associated fuse rating
10 A gG conforming to IEC 60947-5-1
Control circuit voltage limits
0.1...0.25 Uc (-40…70 °C):drop-out DC
0.7...1.25 Uc (-40…60 °C):operational DC
1...1.25 Uc (60…70 °C):operational DC
width (w)
45 mm
mechanical robustness
Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
Net weight
0.58 kg
time constant
28 ms
Hold-in power consumption in w
5.4 W at 20 °C
Mounting support
Plate
Rail
depth
93 mm
inrush power in w
5.4 W (at 20 °C)
mechanical durability
30 Mcycles
Irms rated making capacity
140 A AC conforming to IEC 60947-5-1
250 A DC conforming to IEC 60947-5-1
Maximum operating rate
180 cyc/mn
operating time
53...72 ms coil energisation and NO closing
16...24 ms coil de-energisation and NO opening
47...63 ms coil energisation and NC opening
15...25 ms coil de-energisation and NC closing
minimum switching voltage
17 V
non-overlap time
1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
Pole contact composition
3 NO + 2 NC
Utilisation category
AC-14
AC-15
DC-13
Environment
Ambient air temp for storage/transportation
-60…80 °C
ip degree of protection
IP2X front face conforming to VDE 0106
operating altitude
0...3000 m
ambient air temperature for operation
-40…60 °C
60…70 °C with derating
standards
EN/IEC 60947-5-1
GB/T 14048.5
UL 60947-5-1
CSA C22.2 No 60947-5-1
JIS C8201-5-1
protective treatment
TH conforming to IEC 60068
insulation resistance
> 10 MOhm