Main
Range
ComPacT nouvelle génération
sectioning ability
Oui se conformer à EN/CEI 60947-2
job category
Catégorie A
name of the device
NSX630HB2
type of product or equipment
Disjoncteur
Product Name
ComPacT NSX nouvelle génération
[ui] rated insulation voltage
800 V CA 50/60 Hz
trigger protection functions
LSI
circuit breaker installation mode
Fixe
performance level
HB2 100 kA 690 V CA
neutral pole position
Gauche
trigger name
Micrologic 5.3 E
type of trigger
Électronique
ultimate short-circuit breaking capacity [icu]
100 kA Icu à 500 V CA 50/60 Hz se conformer à CEI 60947-2
100 kA Icu à 525 V CA 50/60 Hz se conformer à CEI 60947-2
100 kA Icu à 660/690 V CA 50/60 Hz se conformer à CEI 60947-2
protected poles
4d
3D + OSN
3d + N/2
3d
Complementary
"no" connection
45 mm
[in] rated operational current
630 A à 40 °C
[ue] rated operational voltage
690 V CA 50/60 Hz
application
Distribution
[ics] rated service breaking capacity
100 kA à 500 V CA 50/60 Hz se conformer à CEI 60947-2
100 kA à 525 V CA 50/60 Hz se conformer à CEI 60947-2
100 kA à 660/690 V CA 50/60 Hz se conformer à CEI 60947-2
short-time protection threshold setting range [isd]
1,5...10 x Ir
Handle front plate colour
255 mm
trigger caliber
630 A à 40 °C
[uimp] rated impulse withstand voltage
8 kV
product weight
8,13 kg
tsd short time protection time delay setting
Réglable 5 positions
electrical life
8000 cycle à 440 V In/2
4000 cycle à 440 V In
6000 cycle à 690 V In/2
2000 cycle à 690 V In
setting the differential protection time delay δt
Réglable 9 positions
type of measurement
Compteur d'énergie
Data recording
Maximètres/minimètres
Valeurs instantanées et de demande
Demande de courant et puissance
Mesure de l'énergie
Qualité d'alimentation
Paramètres de protection et d'alarme
Historiques temps emboutissage et tableaux des événements
Indicateurs de maintenance
mechanical endurance
15000 cycle
width (w)
185 mm
network frequency
50/60 Hz
thermal memory
20 minutes avant et après le déclenchement
Local signalling
pourprêt à fonctionner DEL clignotante (vert)
poursurcharge DEL 105 % Ir (rouge)
poursurcharge DEL 90 % Ir (orange)
long time protection time delay setting range [tr]
15…400 s à 1,5 x Ir
0,5…16 s à 6 x Ir
0,35…11 s à 7,2 x Ir
short time protection time delay setting range [tsd]
0…0,4 s I²t=off
0,1…0,4 s I²t=on
setting range of the long-time protection threshold [ir] (thermal protection)
250...630 A
upstream connection
Façade
downstream connection
Façade
instantaneous protection threshold setting range [ii] (short-circuit protection)
1,5…11 x In
number of slots for electrical auxiliaries
6 slot(s)
mounting bracket
Plaque arrière
neutral protection setting
0,5 x Ir (3d + N/2)
1 x Ir (4d)
1,6 x Ir (3D + OSN)
Aucune protection (3d)
depth (p)
110 mm
Network type
CA
differential protection
Sans
mounting position
Horizontal et vertical
Flat on the back
power loss per pole
39,69 W
tr long time protection time delay setting
Réglable
instantaneous protection sensor setting ii (short circuit protection)
Réglable
ir long time protection sensor setting (thermal protection)
Réglable 9 positions
order type
Par maneton
type of display
Afficheur LCD
kind of protection
L : for protection surcharge (long retard)
S : for protection court retard
I : for protection instantanée contre court-circuit
zsi logic selective latch area
Avec
Poles description
4P
Environment
degree of pollution
3 se conformer à CEI 60664-1
ip degree of protection
IP40 se conformer à CEI 60529
operating altitude
0...2000 m sans réduction de courant
2000 m...5000 m avec réduction de courant
product certificates
CCC
EAC
Marine
class of protection against electric shock
Classe II
operating ambient temperature
-25…70 °C
overvoltage category
Classe II
standards
EN/CEI 60947
relative humidity
0…95 %
shock resistance ik
IK07 se conformer à CEI 62262
storage room temperature
-40…85 °C