Main
Device short name
ComPacT NSX400K
Range
ComPacT
circuit breaker mounting mode
Fixed
Neutral position
Left
Protected poles description
3t
3t + N/2
4t
Trip unit name
Micrologic 2.3
Trip unit technology
Electronic
Trip unit rating
250 A at 40 °C
[ui] rated insulation voltage
1000 V AC 50/60 Hz
Trip unit protection functions
LSoI
performance level
K 10 kA 1000 V AC
Complementary
[ii] instantaneous pick-up adjustment range
3000 A
[in] rated current
250 A at 40 °C
[ue] rated operational voltage
800...1000 V AC 50/60 Hz
[ics] rated service breaking capacity
10 kA at 800 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 1000 V AC 50/60 Hz conforming to IEC 60947-2
Control type
Toggle
depth (d)
110 mm
Product certifications
CE
CCC
[ir] long-time protection pick-up adjustment range
70...250 A
Connection pitch
45 mm
Handle front plate colour
255 mm
Product or component type
Circuit breaker
[isd] short-time protection pick-up adjustment range
1.5...10 x Ir
[uimp] rated impulse withstand voltage
8 kV
[tr] long-time delay adjustment range
11 s at 7.2 x Ir
16 s at 6 x Ir
400 s at 1.5 x Ir
Device application
Special application
Electrical shock protection class
Class II
width (w)
185 mm
network frequency
50/60 Hz
thermal memory
20 minutes before and after tripping
Ik degree of protection
IK07 conforming to IEC 62262
Local signalling
Flashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload
long-time pick-up adjustment type ir (thermal protection)
Adjustable 9 settings
Net weight
7.9 kg
long-time protection delay adjustment type tr
Fixed
Downside connection
Front
number of slots for electrical auxiliaries
6 slot(s)
Earth-leakage protection
Without
Mounting support
Backplate
mechanical durability
15000 cycles
neutral protection setting
0.5 x Ir (3t + N/2)
1 x Ir (4t)
No protection (3t)
electrical durability
1000 cycles at 1000 V In
Network type
AC
instantaneous protection pick-up adjustment type ii
Fixed
Pollution degree
3 conforming to IEC 60664-1
short-time protection delay adjustment type tsd
Fixed
short-time protection pick-up adjustment type isd
Adjustable 9 settings
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Poles description
4P
Upside connection
Front
Utilisation category
Category A
Protection type
L : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
Zone selective interlocking zsi
Without