Main
product range
ComPacT NSX100...250 nouvelle génération
Range
ComPacT nouvelle génération
type of product or equipment
Déclencheur
trigger protection functions
LI
circuit breaker installation mode
Fixe
trigger name
TM-D
type of trigger
Thermique-magnétique
protected poles
3d
Complementary
[ue] rated operational voltage
690 V CA 50/60 Hz
application
Distribution
range compatibility
ComPacT nouvelle génération NSX250
trigger caliber
250 A à 40 °C
network frequency
50/60 Hz
long time protection time delay setting range [tr]
120…400 s à 1,5 x In
15 s à 6 x Ir
setting range of the long-time protection threshold [ir] (thermal protection)
0,7 à 1 x In
instantaneous protection threshold setting range [ii] (short-circuit protection)
5...10 x In
Network type
CA
differential protection
Sans
tr long time protection time delay setting
Fixe
instantaneous protection sensor setting ii (short circuit protection)
Réglable
ir long time protection sensor setting (thermal protection)
Réglable
kind of protection
L : for protection surcharge (thermique)
I : for protection (magnétique) court-circuit
Poles description
3P
Environment
degree of pollution
3 se conformer à CEI 60947-1
ip degree of protection
IP40 se conformer à CEI 60529
class of protection against electric shock
Classe II
operating ambient temperature
-25…70 °C
standards
EN/CEI 60947-2
storage room temperature
-50…85 °C