Main
Range
ComPacT new generation
circuit breaker mounting mode
Fixed
Protected poles description
3D
Trip unit name
TM-G
Trip unit technology
Thermal-magnetic
Trip unit rating
250 A at 40 °C
Trip unit protection functions
LI
Complementary
[ii] instantaneous pick-up adjustment range
625 A
[ue] rated operational voltage
750 V DC
range compatibility
ComPacT new generation NSX100 DC
ComPacT new generation NSX160 DC
ComPacT new generation NSX250 DC
[ir] long-time protection pick-up adjustment range
0.7...1 x In
Product or component type
Trip unit
Device application
Generator
Electrical shock protection class
Class II
long-time pick-up adjustment type ir (thermal protection)
Adjustable
long-time protection delay adjustment type tr
Fixed
Earth-leakage protection
Without
Network type
DC
instantaneous protection pick-up adjustment type ii
Fixed
Pollution degree
3 conforming to IEC 60947-1
Poles description
3P
Protection type
L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Environment
Ambient air temp for storage/transportation
-50…85 °C
ip degree of protection
IP40 conforming to IEC 60529
Range of product
ComPacT NSX100...250 DC new generation
ambient air temperature for operation
-25…70 °C
standards
EN/IEC 60947-2