ComPacT NSX100...250 nouvelle génération
Range
ComPacT nouvelle génération
type of product or equipment
Déclencheur
trigger protection functions
LSIG
circuit breaker installation mode
Fixe
trigger name
Micrologic 6.2 E
type of trigger
Électronique
protected poles
3d
Complementary
[ue] rated operational voltage
690 V CA 50/60 Hz
application
Distribution
electrical data logging
Indicateurs de maintenance
range compatibility
ComPacT nouvelle génération NSX250
short-time protection threshold setting range [isd]
1,5...10 x Ir
trigger caliber
250 A à 40 °C
earth protection time delay setting range [tg]
0…0,4 s I²t=off
0,1…0,4 s I²t=on
earth fault protection threshold setting range [ig]
0,4…1 x In pour In = 40 A
0,2 à 1 x pouce pour In > 40 A
Activation Ig on/off
tsd short time protection time delay setting
Réglable
setting the differential protection time delay δt
Réglable 9 positions
type of measurement
Compteur d'énergie
Data recording
Mesure de l'énergie
Paramètres de protection et d'alarme
Historiques temps emboutissage et tableaux des événements
Valeurs instantanées et de demande
Indicateurs de maintenance
Demande de courant et puissance
Qualité d'alimentation
Maximètres/minimètres
network frequency
50/60 Hz
thermal memory
20 minutes avant et après le déclenchement
Local signalling
pourprêt à fonctionner DEL clignotante (vert)
poursurcharge DEL 105 % Ir (rouge)
poursurcharge DEL 90 % Ir (orange)
setting the earth fault protection time delay tg
Réglable
long time protection time delay setting range [tr]
15…400 s à 1,5 x Ir
0,35…11 s à 7,2 x Ir
0,5…16 s à 6 x Ir
short time protection time delay setting range [tsd]
0…0,4 s I²t=off
0,1…0,4 s I²t=on
setting range of the long-time protection threshold [ir] (thermal protection)
100...250 A
instantaneous protection threshold setting range [ii] (short-circuit protection)
1,5…12 x In
ig earth fault protection sensor setting
Réglable
Network type
CA
differential protection
Sans
tr long time protection time delay setting
Réglable
instantaneous protection sensor setting ii (short circuit protection)
Réglable
ir long time protection sensor setting (thermal protection)
Réglable 9 positions
type of display
Afficheur LCD
kind of protection
L : for protection surcharge (long retard)
S : for protection court retard
I : for protection instantanée contre court-circuit
G : for protection court-circuit à la masse
zsi logic selective latch area
Avec
Poles description
3P