Main
Range
ComPacT nouvelle génération
sectioning ability
Oui se conformer à EN/CEI 60947-2
job category
Catégorie A
name of the device
NSX160 DC PV
type of product or equipment
Disjoncteur
Product Name
ComPacT NSX DC PV
[ui] rated insulation voltage
1000 V CC se conformer à CEI 60947-2
trigger protection functions
LI
circuit breaker installation mode
Fixe
performance level
F 10 kA 1000 V CC
trigger name
TM-DC
type of trigger
Thermique-magnétique
ultimate short-circuit breaking capacity [icu]
10 kA Icu à 1000 V CC 4 pôles en série se conformer à CEI 60947-2
Complementary
"no" connection
35 mm
[in] rated operational current
160 A à 40 °C
[ue] rated operational voltage
1000 V CC
application
Photovoltaïque
[ics] rated service breaking capacity
10 kA à 1000 V CC se conformer à CEI 60947-2
Handle front plate colour
161 mm
trigger caliber
160 A à 40 °C
[uimp] rated impulse withstand voltage
8 kV se conformer à CEI 60947-2
product weight
2,8 kg
electrical life
1000 cycle à 1000 V In
mechanical endurance
10000 cycle
width (w)
140 mm
setting range of the long-time protection threshold [ir] (thermal protection)
0,7 à 1 x In
upstream connection
Façade
downstream connection
Façade
instantaneous protection threshold setting range [ii] (short-circuit protection)
1250 A
mounting bracket
Plaque arrière
depth (p)
186 mm
Network type
CC
differential protection
Sans
mounting position
Horizontal et vertical
Flat on the back
tr long time protection time delay setting
Fixe
instantaneous protection sensor setting ii (short circuit protection)
Fixe
ir long time protection sensor setting (thermal protection)
Réglable
order type
Par maneton
kind of protection
L : for protection surcharge (thermique)
I : for protection (magnétique) court-circuit
Poles description
4P
Environment
degree of pollution
3 se conformer à CEI 60664-1
ip degree of protection
IP40 se conformer à CEI 60529
operating altitude
0...2000 m sans réduction de courant
2000 m...5000 m avec réduction de courant
product certificates
CCC
EAC
Marine
class of protection against electric shock
Classe II
operating ambient temperature
-25…70 °C
overvoltage category
Classe II
standards
EN/CEI 60947
relative humidity
0…95 %
shock resistance ik
IK07 se conformer à CEI 62262
storage room temperature
-50…85 °C