SPECIFICATIONS
Main
Range ComPacT nouvelle génération
sectioning ability Oui se conformer à EN/CEI 60947-2
job category Catégorie A
name of the device NSX160F
type of product or equipment Disjoncteur
Product Name ComPacT NSX nouvelle génération
[ui] rated insulation voltage 800 V CA 50/60 Hz
trigger protection functions LSoI
circuit breaker installation mode Fixe
performance level F 36 kA 415 V CA
neutral pole position Gauche
trigger name Micrologic 2.2
type of trigger Électronique
ultimate short-circuit breaking capacity [icu] 85 kA Icu à 220/240 V CA 50/60 Hz se conformer à CEI 60947-2
36 kA Icu à 380/415 V CA 50/60 Hz se conformer à CEI 60947-2
35 kA Icu à 440 V CA 50/60 Hz se conformer à CEI 60947-2
30 kA Icu à 500 V CA 50/60 Hz se conformer à CEI 60947-2
22 kA Icu à 525 V CA 50/60 Hz se conformer à CEI 60947-2
8 kA Icu à 660/690 V CA 50/60 Hz se conformer à CEI 60947-2
35 kA à 480 V CA 50/60 Hz se conformer à UL 508
protected poles 4d
3d + N/2
3d
Complementary
"no" connection 35 mm
[in] rated operational current 160 A à 40 °C
[ue] rated operational voltage 690 V CA 50/60 Hz
application Distribution
[ics] rated service breaking capacity 85 kA à 220/240 V CA 50/60 Hz se conformer à CEI 60947-2
36 kA à 380/415 V CA 50/60 Hz se conformer à CEI 60947-2
35 kA à 440 V CA 50/60 Hz se conformer à CEI 60947-2
30 kA à 500 V CA 50/60 Hz se conformer à CEI 60947-2
22 kA à 525 V CA 50/60 Hz se conformer à CEI 60947-2
8 kA à 660/690 V CA 50/60 Hz se conformer à CEI 60947-2
short-time protection threshold setting range [isd] 1,5...10 x Ir
Handle front plate colour 161 mm
trigger caliber 160 A à 40 °C
[uimp] rated impulse withstand voltage 8 kV
product weight 2,6 kg
tsd short time protection time delay setting Fixe
electrical life 40000 cycle à 440 V In/2
20000 cycle à 440 V In
15000 cycle à 690 V In/2
7500 cycle à 690 V In
setting the differential protection time delay δt Réglable 9 positions
mechanical endurance 40000 cycle
width (w) 140 mm
network frequency 50/60 Hz
thermal memory 20 minutes avant et après le déclenchement
Local signalling pourprêt à fonctionner DEL clignotante (vert)
poursurcharge DEL 105 % Ir (rouge)
poursurcharge DEL 90 % Ir (orange)
long time protection time delay setting range [tr] 400 s à 1,5 x Ir
16 s à 6 x Ir
11 s à 7,2 x Ir
setting range of the long-time protection threshold [ir] (thermal protection) 63...160 A
upstream connection Façade
downstream connection Façade
instantaneous protection threshold setting range [ii] (short-circuit protection) 2400 A
number of slots for electrical auxiliaries 5 slot(s)
mounting bracket Plaque arrière
neutral protection setting 0,5 x Ir (3d + N/2)
1 x Ir (4d)
Aucune protection (3d)
depth (p) 86 mm
Network type CA
differential protection Sans
mounting position Horizontal et vertical
Flat on the back
power loss per pole 9,22 W
tr long time protection time delay setting Fixe
instantaneous protection sensor setting ii (short circuit protection) Fixe
ir long time protection sensor setting (thermal protection) Réglable 9 positions
order type Par maneton
kind of protection L : for protection surcharge (long retard)
So : for protection court retard avec retard fixe
I : for protection instantanée contre court-circuit
zsi logic selective latch area Sans
Poles description 4P
Environment
degree of pollution 3 se conformer à CEI 60664-1
ip degree of protection IP40 se conformer à CEI 60529
operating altitude 0...2000 m sans réduction de courant
2000 m...5000 m avec réduction de courant
product certificates CCC
EAC
Marine
class of protection against electric shock Classe II
operating ambient temperature -25…70 °C
overvoltage category Classe II
standards EN/CEI 60947
relative humidity 0…95 %
shock resistance ik IK07 se conformer à CEI 62262
storage room temperature -50…85 °C