Device short name
NSX160B
Range
ComPacT new generation
circuit breaker mounting mode
Fixed
Neutral position
Left
Protected poles description
3D
Product Name
ComPacT NSX new generation
Trip unit name
TM-D
Trip unit technology
Thermal-magnetic
Trip unit rating
160 A at 40 °C
[ui] rated insulation voltage
800 V AC 50/60 Hz
Trip unit protection functions
LI
performance level
B 25 kA 415 V AC
Complementary
[ii] instantaneous pick-up adjustment range
1250 A
[in] rated current
160 A at 40 °C
[ue] rated operational voltage
690 V AC 50/60 Hz
[ics] rated service breaking capacity
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Control type
Toggle
depth (d)
86 mm
Product certifications
CCC
EAC
Marine
[ir] long-time protection pick-up adjustment range
0.7...1 x In
Connection pitch
35 mm
Handle front plate colour
161 mm
Product or component type
Circuit breaker
[uimp] rated impulse withstand voltage
8 kV
[tr] long-time delay adjustment range
120…400 s at 1.5 x In
15 s at 6 x Ir
Device application
Distribution
Electrical shock protection class
Class II
width (w)
140 mm
network frequency
50/60 Hz
Ik degree of protection
IK07 conforming to IEC 62262
long-time pick-up adjustment type ir (thermal protection)
Adjustable
Net weight
2.6 kg
long-time protection delay adjustment type tr
Fixed
Downside connection
Front
number of slots for electrical auxiliaries
5 slot(s)
Earth-leakage protection
Without
Mounting support
Backplate
power dissipation per pole
13.95 W
mechanical durability
40000 cycles
neutral protection setting
No protection (3D)
electrical durability
40000 cycles at 440 V In/2
20000 cycles at 440 V In
15000 cycles at 690 V In/2
7500 cycles at 690 V In
Network type
AC
instantaneous protection pick-up adjustment type ii
Fixed
Pollution degree
3 conforming to IEC 60664-1
mounting position
Horizontal and vertical
Flat on the back
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Poles description
4P
Upside connection
Front
Utilisation category
Category A
Protection type
L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Environment
Ambient air temp for storage/transportation
-50…85 °C
ip degree of protection
IP40 conforming to IEC 60529
operating altitude
0...2000 m without derating
2000 m...5000 m with derating
ambient air temperature for operation
-25…70 °C
overvoltage category
Class II
standards
EN/IEC 60947
relative humidity
0…95 %