Main
product range
ComPacT NSX100...250 nouvelle génération
Range
ComPacT nouvelle génération
type of product or equipment
Déclencheur
trigger protection functions
LSI
circuit breaker installation mode
Fixe
neutral pole position
Gauche
trigger name
Micrologic 7.2 E AL
type of trigger
Électronique
protected poles
3d + N/2
4d
3d
Complementary
specific differential protection mode
Off utilisation de l'interrupteur rotatif IΔn
[ue] rated operational voltage
440 V CA 50/60 Hz
application
Distribution
range compatibility
ComPacT nouvelle génération NSX160
ComPacT nouvelle génération NSX250
short-time protection threshold setting range [isd]
1,5...10 x Ir
differential protection sensitivity setting range [iОґn]
0,03 A
0,1 A
0,3 A
0,5 A
1 A
3 A
5 A
trigger caliber
160 A à 40 °C
tsd short time protection time delay setting
Réglable
setting the differential protection time delay δt
Réglable
type of measurement
Compteur d'énergie
differential protection time delay setting range [Δt]
0 ms
60 ms
150 ms
500 ms
1 s
Data recording
Mesure de l'énergie
Indicateurs de maintenance
Historiques temps emboutissage et tableaux des événements
Paramètres de protection et d'alarme
Valeurs instantanées et de demande
Rapport de test
Qualité d'alimentation
Conduit de fuite à la terre
Maximètres/minimètres
Demande de courant et puissance
iδn differential protection sensitivity adjustment
Réglable
network frequency
50/60 Hz
thermal memory
20 minutes avant et après le déclenchement
Local signalling
pourprêt à fonctionner DEL clignotante (vert)
poursurcharge DEL 105 % Ir (rouge)
poursurcharge DEL 90 % Ir (orange)
long time protection time delay setting range [tr]
15…400 s à 1,5 x Ir
0,35…11 s à 7,2 x Ir
0,5…16 s à 6 x Ir
short time protection time delay setting range [tsd]
0…0,4 s
setting range of the long-time protection threshold [ir] (thermal protection)
63...160 A
instantaneous protection threshold setting range [ii] (short-circuit protection)
1,5 à 15 x In
neutral protection setting
0,5 x Ir (3d + N/2)
1 x Ir (4d)
Aucune protection (3d)
Network type
Classe A
differential protection
Intégrée
tr long time protection time delay setting
Réglable
instantaneous protection sensor setting ii (short circuit protection)
Réglable
ir long time protection sensor setting (thermal protection)
Réglable 9 positions
type of display
Afficheur LCD
kind of protection
L : for protection surcharge (long retard)
S : for protection court retard
I : for protection instantanée contre court-circuit
zsi logic selective latch area
Sans
Poles description
4P