Main
product range
ComPacT NSX100...250 nouvelle génération
Range
ComPacT nouvelle génération
type of product or equipment
Déclencheur
trigger protection functions
LSI
circuit breaker installation mode
Fixe
neutral pole position
Gauche
trigger name
Micrologic 5.2 E
type of trigger
Électronique
protected poles
3d + N/2
4d
3D + OSN
3d
Complementary
[ue] rated operational voltage
690 V CA 50/60 Hz
application
Distribution
electrical data logging
Indicateurs de maintenance
range compatibility
ComPacT nouvelle génération NSX160
ComPacT nouvelle génération NSX250
short-time protection threshold setting range [isd]
1,5...10 x Ir
trigger caliber
160 A à 40 °C
tsd short time protection time delay setting
Réglable
setting the differential protection time delay δt
Réglable 9 positions
type of measurement
Compteur d'énergie
Data recording
Mesure de l'énergie
Paramètres de protection et d'alarme
Historiques temps emboutissage et tableaux des événements
Valeurs instantanées et de demande
Indicateurs de maintenance
Demande de courant et puissance
Qualité d'alimentation
Maximètres/minimètres
network frequency
50/60 Hz
thermal memory
20 minutes avant et après le déclenchement
Local signalling
pourprêt à fonctionner DEL clignotante (vert)
poursurcharge DEL 105 % Ir (rouge)
poursurcharge DEL 90 % Ir (orange)
long time protection time delay setting range [tr]
15…400 s à 1,5 x Ir
0,35…11 s à 7,2 x Ir
0,5…16 s à 6 x Ir
short time protection time delay setting range [tsd]
0…0,4 s I²t=off
0,1…0,4 s I²t=on
setting range of the long-time protection threshold [ir] (thermal protection)
63...160 A
instantaneous protection threshold setting range [ii] (short-circuit protection)
1,5 à 15 x In
neutral protection setting
0,5 x Ir (3d + N/2)
1 x Ir (4d)
1,6 x Ir (3D + OSN)
Aucune protection (3d)
Network type
CA
differential protection
Sans
tr long time protection time delay setting
Réglable
instantaneous protection sensor setting ii (short circuit protection)
Réglable
ir long time protection sensor setting (thermal protection)
Réglable 9 positions
type of display
Afficheur LCD
kind of protection
L : for protection surcharge (long retard)
S : for protection court retard
I : for protection instantanée contre court-circuit
zsi logic selective latch area
Avec
Poles description
4P
Environment
degree of pollution
3 se conformer à CEI 60947-1
ip degree of protection
IP40 se conformer à CEI 60529
class of protection against electric shock
Classe II
standards
EN/CEI 60947-2
operating ambient air temperature
-25…70 °C
storage room temperature
-40…85 °C